- 18
-
2)
Half-cut
Figure 8: PV module installed at long and short side with Clamp fitting method
Module
type
Cell type
Cell
quantity
Dimension(mm)
A*B
J
K
M
N
Frame
Group 2
6 inch Poly
6*20
1665*992 & 1684*1002
50
240
400
420
40*35 & 35*35
Group 5
6 inch Poly
6*24
1987*992 & 2000*992 & 2008*1002 50
240
400
420
40*35 & 35*35
Group 8
6 inch Mono
6*20
1665*992 & 1684*1002
50
240
400
480
40*35
Group 11
6 inch Mono
6*24
1987*992 & 2000*992 & 2008*1002 50
240
400
480
40*35
Table 8: Mechanical dimensions when modules installed at long and short sides with Clamp fitting method
3. Wiring and connection
a) Before this procedure, please read the operation instructions of the PV system carefully.
Make wiring by Multi-connecting cables between the PV modules in series or parallel
connection, which is determined by user‟s configuration requirement for system power,
current and voltage.
b) PV modules connected in series should have similar current, and modules must not be
connected together to create a voltage higher than the permitted system voltage. The
maximum number of modules in series depends on system design, the type of inverter
used and environmental conditions.
c) The maximum fuse rating value in an array string can be found on the product label or in
the product datasheet. The fuse rating value is also corresponding to the maximum
reverse current that a module can withstand, i.e. when one string is in shade then the other
parallel strings of modules will be loaded by the shaded string and the current will pass