LINE
HIGH VOLTAGE
MOTOR WIRING DIAGRAM
230V, SINGLE PHASE, 50/60 Hz
Before doing any electrical work, make certain that
all power sources are disconnected and properly
tagged or locked out per OSHA regulations. All
electrical work must be done by a qualified
technician and must meet all applicable codes.
Failure to do so could result in electrical shock,
serious injury or death.
WARNING
!
SINGLE PHASE 230V ELECTRICAL SCHEMATIC
WIRE CONNECTIONS (IN FIELD):
15amp Disconnect to Terminal Block Connections
Disconnect L1 to A105 (Black 12ga.)
Disconnect L2 to A103 (Red 12ga.)
Disconnect Ground to A113 (Green 12ga.)
Terminal Block to Motor Box
A111 to T1 & T4 on Motor (Black 12ga.)
A112 to T2 & T3 on Motor (Red 12ga.)
A114 to Ground on Motor (Green 12ga.)
A109 to Black Wire on Solenoid 1 (Black 18ga.)
A110 to Black Wire on Solenoid 2 (Black 18ga.)
A106 to White Wire on Solenoid 1 (White 18ga.)
A107 to White Wire on Solenoid 2 (White 18ga.)
(Both White Wires from solenoids can be tied together only
needing one connection to A106 or A107)
A101 to Green Wire on Solenoid 1 (Green 18ga.)
A102 to Green Wire on Solenoid 2 (Green 18ga.)
(Both Ground wires from solenoids can be tied together only
needing one connection to A101 or A102)