KI-OM-0591 Rev 3
15
Operations
Figure 3 Graph of Temperature Loss vs. Umbilical Length
Note
The above graph is based on the approximate temperature loss through a 1/2”
Synflex or equivalent, used in conditions with 2 - 5ºC (35 - 45ºF) water temperature.
4
Determine temperature rise required (T
rise
).
To determine the required temperature rise (T
rise
) through the unit, subtract the inlet
temperature (T
in
) from the required total outlet temperature (T
out
) calculated in step 3.
5
Heater bank selection.
After calculating T
rise
use the table in Table 3 to determine the heater banks to be used.
Locate the temperature rise in the left column. Read across to determine which heaters are
required to achieve the temperature rise. A tick indicates that a heater bank should be
switched on.
Содержание WHE - 3
Страница 2: ......
Страница 6: ...vi KI OM 0591 Rev 3 Intentionally blank ...
Страница 8: ...viii KI OM 0591 Rev 3 Intentionally blank ...
Страница 46: ...38 KI OM 0591 Rev 3 Part Identification Intentionally blank ...
Страница 56: ...B 2 KI OM 0591 Rev 3 Intentionally blank ...
Страница 60: ...C 4 KI OM 0591 Rev 3 WWHE 3 Electrical Schematic 24 VDC Control Circuit With Remote Sheet 1 of 2 ...
Страница 61: ...KI OM 0591 Rev 3 C 5 Sheet 2 of 2 ...
Страница 62: ...C 6 KI OM 0591 Rev 3 WHE 3 Electrical Schematic 440 V Heater Circuit With Remote ...
Страница 63: ...KI OM 0591 Rev 3 C 7 WHE 3 Electrical Schematic With Remote Busbar Manufacturing Detail ...
Страница 64: ...C 8 KI OM 0591 Rev 3 Schematic Water Heater Electric WHE 3 Upgrade With PV S 3 1 Cert Sheet 1 of 2 ...
Страница 65: ...KI OM 0591 Rev 3 C 9 Sheet 2 of 2 ...
Страница 66: ...C 10 KI OM 0591 Rev 3 Schematic Water Heater Electric WHE 3 Upgrade With PV S 3 2 Cert Sheet 1 of 2 ...
Страница 67: ...KI OM 0591 Rev 3 C 11 Sheet 2 of 2 ...
Страница 68: ...C 12 KI OM 0591 Rev 3 Intentionally blank ...