A.2
KI-OM-0591 Rev 3
To enter the Setup Setting Mode, press the Shift (MODE) key while pressing the SET key.
Move through the parameters by pressing the SET key. Use the mode key to highlight a digit
and use the arrow keys to change the highlighted digit.
Table 2
Setup Setting Mode
Temperature
Controller
Setup Setting Mode
Function
Block
Parameter
Spec.
Value
Description
Code
Description
HbA1
Heater break alarm 1 set point
0 (off)
Unused
Hbl1
Heater break alarm determination
point 1
30
Unused
HbH1
Heater melting determination point 1
30
Unused
HbA2
Heater break alarm 2 set point
0 (off)
Unused
Hbl2
Heater break alarm determination
point 2
30
Unused
HbH2
Heater melting determination point 2
30
Unused
Pb
PV Bias
0
Range/Sensitivity of PV scale
dF
PV Digital filter
0(off)
Pr
PV Ratio
1
Rotation of PV scale
PLC
PV Low input cut-off
0
Unused
rb
RS Bias
30.0
Range/Sensitivity of RS scale
(lncrease=lncrease of range)
dF2
RS Digital filter
0 (off)
rr
RS Ratio
0.330
Rotation of RS scale
(increase=anticlock)
T
Proportional cycle time (heat-side)
20
Unused
t
Proportional cycle time (cool-side)
20
Unused
Add1
Device address 1
0
Unused
bPS1
Communication Speed 1
19.2
Unused
b1T1
Data bit configuration 1
8n1
Unused
lnT1
Interval time 1
10
Unused
Add2
Device address 2
0
Unused
bPS2
Communication Speed 2
19.2
Unused
b1T2
Data bit configuration 2
8n1
Unused
lnT2
Interval time 2
10
Unused
LCK
Set lock level
0000
To lock functionality of keypad
Содержание WHE - 3
Страница 2: ......
Страница 6: ...vi KI OM 0591 Rev 3 Intentionally blank ...
Страница 8: ...viii KI OM 0591 Rev 3 Intentionally blank ...
Страница 46: ...38 KI OM 0591 Rev 3 Part Identification Intentionally blank ...
Страница 56: ...B 2 KI OM 0591 Rev 3 Intentionally blank ...
Страница 60: ...C 4 KI OM 0591 Rev 3 WWHE 3 Electrical Schematic 24 VDC Control Circuit With Remote Sheet 1 of 2 ...
Страница 61: ...KI OM 0591 Rev 3 C 5 Sheet 2 of 2 ...
Страница 62: ...C 6 KI OM 0591 Rev 3 WHE 3 Electrical Schematic 440 V Heater Circuit With Remote ...
Страница 63: ...KI OM 0591 Rev 3 C 7 WHE 3 Electrical Schematic With Remote Busbar Manufacturing Detail ...
Страница 64: ...C 8 KI OM 0591 Rev 3 Schematic Water Heater Electric WHE 3 Upgrade With PV S 3 1 Cert Sheet 1 of 2 ...
Страница 65: ...KI OM 0591 Rev 3 C 9 Sheet 2 of 2 ...
Страница 66: ...C 10 KI OM 0591 Rev 3 Schematic Water Heater Electric WHE 3 Upgrade With PV S 3 2 Cert Sheet 1 of 2 ...
Страница 67: ...KI OM 0591 Rev 3 C 11 Sheet 2 of 2 ...
Страница 68: ...C 12 KI OM 0591 Rev 3 Intentionally blank ...