Jetter AG
Parameterization | 8
User Manual – JXM-IO-E30
46 / 70
Status information
Index
Subindex
Description
Type
Types of access
0x1001
0
Error register
U8
R
Bit 0
General error
R
Bit 1
Total overcurrent
R
Bit 3
Temperature
R
Bit 4
Communication error
R
Bit 7
CI error (invalid input)
R
Tab. 39:
Status information
8.4 Saving settings permanently and resetting to default values
The following parameters are permanently stored in the EEPROM:
■
PDO mapping
■
All I/O interface assignments and parameters
■
Producer heartbeat time
Save settings
Index
Subindex
Description
Type
Types of
access
Default
value
0x1010
0
Number of supported entries
U8
R
1
1
Saving all parameters
U32
R/W
When the specific signature 0x65766173 ("save") is written, the pa-
rameters are saved.
Tab. 40:
Save settings in EEPROM
Resetting the settings to their default values
Index
Subindex
Description
Type
Types of
access
Default
value
0x1011
0
Number of supported entries
U8
R
1
1
Command register
U32
R/W
1
When the specific signature 0x64616F6C ("load") is written, all
settings are reset to the default values.
Tab. 41:
Resetting the settings to their default values
INFO
Loading the settings from the EEPROM
During bootup, the last saved settings are automatically loaded.
During a firmware update, the settings may be reset to the default values.