Jetter AG
Registers - Overview | 8
JX3-THI2-RTD-EI User Manual
24 / 36
Module register
0003
Description
Digitized value of temperature input channel # 2
Type of access
Read access
Data type
Float
Value after reset
Analog value of temperature input # 2
Default value
The measured value is displayed in °C. The unit can be
configured via
8.5 Temperature inputs - Command registers
Module register
1y01
Description
Command register
Commands let you enable or disable various functions of
the module.
y = Temperature input # 1 or 2
Type of access
Read/write
Value range
8 bits
Value after reset
0
Com-
mand
Description
6
Reset
Reset in the case of cable breakage, short-circuit, excess or insuffi-
cient temperature
70
Resetting the lower limit value during min./max. value storage
71
Resetting the upper limit value during min./max. value storage
72
Resetting both limit values during min./max. value storage
102
Enabling two-wire mode
The line resistance is included as an error in the measurement re-
sult.
103
Enabling three-wire mode
The resistance of a line is measured and compensated.
104
Enabling four-wire mode
The resistance of both lines is measured separately and compen-
sated.
105
Fast Mode
Measurement in approx. 10 ms
106
Slow Mode
Measurement in approx. 100 ms
107
Switching the display to degrees centigrade
108
Switching the display to Fahrenheit
109
PT100
Changing the measurement to PT100
110
PT1000
Changing the measurement to PT1000
111
This instruction is for re-acquiring the line resistance R
L
112
Disabling the channel
Re-enabling via commands
102, 103, 104, 109, 110, 111