JX3-THI2-RTD-EI User Manual
26 / 36
Bit values
Description
Bit 3
4-wire measurement
0= Disabled
1= Enabled
Bit 5
Measuring mode
0= Slow measuring mode (approx. 100 ms for a new reading)
1= Fast measuring mode (approx. 10 ms for a new reading)
Bit 6
Validity of values of the given channel
0= Invalid values
1= Valid values
Bit 7
Channel Calibration
0= Not calibrated
1= Calibrated
Bit 8
Forcing
0= Disabled
1= Enabled
Bit 9
Type of thermal sensor
0= Pt1000
1= Pt100
Bit 11
Resistance value indication
0= Resistance is displayed in module register 0002, respectively
0003
1= Temperature value is displayed in module register 0002, respec-
tively 0003.
Bit 12
Calibration mode
0= Disabled
1= Enabled
Bit 13
Potentiometer mode
0= Disabled
1= Enabled
Bit 14
Channel enabled/disabled
0= Disabled
1= Enabled
Bit 15
Reset
0= No reset/normal measuring mode
1= Initiating a reset (synchronously)
8.7 Force value
When forcing, the value from module register 1y04 is transferred to the controller
instead of the analog value of a connected sensor. This way, the behavior of the
connected sensor can be simulated during commissioning. This option allows
also to test exceptional situations which do not occur during normal operation.
Activating and deactivating the Force function for an analog input and further in-
formation on this topic can be found under
Temperature inputs - Command regis-
Module register
1y04
Force value
Description
Simulated value of temperature input Y
Type of access
Read/write