VAC Controller CVS/VIP
Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143
Doc. Rev.: 5 (2020-11-30)
9
Main Menu 2 Settings
● Active Alarm 2.1
Displays the 'current" date and time and will list any active alarms in the system.
___________________________________________________________________________________________________________________
● Alarm history 2.2
Use the up and down arrow keys to view a history log, including dates and times, of the last 100 alarms.
The newest alarm will show in the display when the history log opens.
___________________________________________________________________________________________________________________
● Alarm setting 2.3
2.3.1 - Long running time
Default: 10 minutes
Maximum constant pump running time: 1-60
minutes
2.3.2 - Low vacuum alarm
Default: 20%
Low vacuum alarm: 0-30%
2.3.3 - Runtime after full tank
Default: 0 minutes
Maximum time it is possible to run the pump after
the high level tank alarm has been activated.
When this runtime expires, the pump will stop.
Empty the tank.
___________________________________________________________________________________________________________________