VAC Controller CVS/VIP

Tel. +47 70 03 91 00

www.jetsgroup.com

Product No. 121315143

Doc. Rev.: 5 (2020-11-30)

2

Function and Principle

The VAC Controller is programmed to control the following:

● Automatic start and stop of a Vacuumarator™ pump.

● Manual start and stop of a Vacuumarator™ pump. 

● Vacuum level monitoring.

● Auto stop after delayed run time (default 10 min).

● Tank level monitoring from a level switch in a tank.

● Activation of an alarm signal.

● Ready signal from a presence sensor (optional). Starts the Vacuumarator™ pump and produces vacuum to a set vacuum level.

Alarm

The VAC Controller is programmed with the following alarm settings:

● Power ON - Engages closed contact at alarm output F.

● Low Vacuum - Engages and activates alarm output G.

● Full Tank - Alarm is based on a level indication from a tank. Requires a level switch (not included).

● Long Running Time - Engages and activates alarm output I.

● Vacuum Transmitter Fault - Alarm is based on vacuum transmitter not connected, connected wrong, not working.

● Full Tank Warning - If the time setting in "runtime after full tank" has been set over 00, a pre-warning alarm will sound. This means that the 

pump will run in xx-minutes before the full tank alarm sounds. Start planning to have the tank emptied.

Operation

● AUTO Mode 1.1

When the system is intended to be used as a constant vacuum system (CVS), and the motion/presence sensors are not connected to the 
VAC Controller.

● VIP Mode 1.2

When the system is used with motion/presence sensors that are connected to the VAC Controller. Vacuum is produced when activating the 
zone of the motion sensor.

● Manual Mode 1.3

Starts and stops the Vacuumarator™ pump via the VAC Controller, regardless of the vacuum transmitter (vacuum level).

WARNING: This can cause the vacuum to reach a very high level in the system and the pump will not stop.

● OFF Mode 1.4

System OFF, the VAC Controller will not start in this mode.

Содержание 121315143

Страница 1: ...ed herein is solely for information purposes does not constitute any warranty or representation of any kind and is subject to change without notice We strive to reproduce product colors reasonably accurate Without prior written approval this document or any part of may not be reproduced in any form Jets Vacuumarator Helivac VC VOD CVS and Softsound are trademarks and or registered trademarks of Je...

Страница 2: ...ng Time Engages and activates alarm output I Vacuum Transmitter Fault Alarm is based on vacuum transmitter not connected connected wrong not working Full Tank Warning If the time setting in runtime after full tank has been set over 00 a pre warning alarm will sound This means that the pump will run in xx minutes before the full tank alarm sounds Start planning to have the tank emptied Operation AU...

Страница 3: ...ning Avoid touching the connector with wet hands Do not disconnect the plug by pulling the electrical cord 2 14 Warning The equipment safety is guaranteed only if used in compliance with the instructions provided Do not exceed the limits provided 6 11 Notice Immediately upon receipt check the equipment for external damage Any damage detected after dispatch should be reported immediately to Jets Va...

Страница 4: ...al information in this document The document contains important information related to the installation and settings for your installation Electrical Connections Diagram A Pre wired B Signal cable to the Vacuumarator pump C Vacuum transmitter D VIP signal optional E Tank level optional F Alarm Power on normally open contact G Alarm Low vacuum H Alarm Full tank I Alarm Long running time J Optional ...

Страница 5: ... Installation Steps 1 Insert a screwdriver into both of the slots on the front cover to open the controller 2 Lift the display out of the housing 3 Using the four screw holes in the corners of the housing secure the controller to the wall screws not provided 4 Return the display back into position on the housing 5 Close both side covers Ensure both sides are locked in place ...

Страница 6: ...Done to save The blinking will stop and the value will be saved Each time a keystroke activates a button a small beep will be heard if the alarm sound is turned on off in menu 2 6 8 Press and hold the return button for 5 seconds to restart the VAC Controller The controller s long running time and warning tank level values will reset Press the return button to go back to the main menu Factory Setti...

Страница 7: ...umarator pump s power is disconnected the VAC Controller s power must also be disconnected 3 28 Warning Never work on the equipment when power is applied Setting Selections 1 Menu screen 2 Return Reset button 3 Scroll down button 4 Scroll right button 5 Scroll left button 6 Scroll up button 7 OK Save selection button 8 Power light Main Menu Vacuum Level Shows the current vacuum level Menu To enter...

Страница 8: ...ent vacuum level 1 3 Manual Mode Manual start and stop of the Vacuumarator pump 1 4 System OFF ___________________________________________________________________________________________________________________ Main Menu 2 Selecting Menu from the main menu screen will take you to Main Menu 2 Alarm Alarm history Alarm setting Vacuum setting VIP setting Operation data Language Factory setting 2 1 2 ...

Страница 9: ...newest alarm will show in the display when the history log opens ___________________________________________________________________________________________________________________ Alarm setting 2 3 2 3 1 Long running time Default 10 minutes Maximum constant pump running time 1 60 minutes 2 3 2 Low vacuum alarm Default 20 Low vacuum alarm 0 30 2 3 3 Runtime after full tank Default 0 minutes Maximu...

Страница 10: ...twen set point in xx minutes after activated sensor or level switch 1 60 minutes ___________________________________________________________________________________________________________________ Operation data 2 6 2 6 1 Date Press OK and the value will blink Arrow up and down and press OK to set the day month and year 2 6 2 Time Press OK and the value will blink Arrow up and down and press OK to...

Страница 11: ...ontroller Alarm sound ON default OFF function will deactivate all the sound from the controller alarm and key stroke sounds Alarm outputs NC default normally closed NO normally open alarm output Choose if alarm output long running time full tank and low vacuum should be normally open or normally closed Alarm output Power ON should always be pre set at NO and is not included in this selection This ...

Страница 12: ...high level tank signal input is active closed signal The pump does not stop immediately but a running time count starts runtime after full tank alarm The runtime time is adjustable in the settings menu 2 3 3 The counter will be reset by a power failure The full tank alarm is activated The runtime after full tank time in alarm setting 2 3 3 can be adjusted Start planning to have the tank emptied Fu...