6.4 Controller activation and deactivation
The controller can be activated and deactivated directly from the measurement value
display by pressing the
key. With this, operation is changed from manual (controller
OFF) to automatic (controller ON) and vice versa. The current operating mode will appear
on the display.
WARNING!
Ensure that the controller is deactivated before connecting metering pumps or
other similar devices to the unit!
6.5 Turn-on delay
With the Turn-on delay, upon putting the device into operation the first time or on subse-
quent occasions or after disconnection from the main power supply, you can enter a time
which must elapse before the controller becomes active. This delay time gives the measu-
ring processes time to settle and stabilise, thereby preventing false metering incidents in
the device start-up phases.
6.6 External controller stop
It is also possible to switch the device ON and OFF externally. No settings are required to
do so. You must simply connect an external switch to the digital input. When the input is
opened, the controller stops and the “Water Deficiency” message will come up on display.
NOTE!
This function can also be utilised as a water deficiency protection by connecting
a float gauge.
.
.