| Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings
6. P-/PI-Controller as pulse-frequency controller
Different controller settings can be selected for S1 and S2.
The following parameters must be set for the Pulse-frequency controller:
1) Set points S1 and S2
S1 corresponds to Relay 1, S2 to Relay 2.
2) P range and Integral time for S1 and S2
Enter a P range > 0.
For a P-Controller it is necessary that Integral time = 0,
for a PI-Controller the Integral time must be > 0.
3) Pulse-frequency for S1 and S2
Preset the maximum pulse frequency, which would correspond to a metering of
100%.
4) Effective operating direction for S1 and S2
Set the “raise“ option, if metering increases the measurement value.
Set the “lower” option if metering decreases the measurement value.
.
.
Controller settings
.
.
.
Basic settings
.
.
Contr. Settings
Puls-freq. S1
00*100/h
Puls-freq. S2
00*100/h
Direction S1
raise
Direction S2
lower
Main menu
Basic settings
Controller settingss
Set point S1
0.50 mg/l
P range S1
0.20 mg/l
Integral time S1
000 sec.
Sollwert S2
0.00 mg/l
P range S2
0.20 mg/l
Integral time S2
000 sec.
Set point