3.3.2.
Fixing the DEACTIVATION magnet
With the GATE AT 30-50CM FROM ITS CLOSED POSITION:
Black magnet must be fixed at the other extreme of the gate (in respect of the grey magnet). The location of this magnet
depends on the inhibition zone desired.
Due to NO TOUCH detection, it is required that an inhibition zone is created at the end of the gate movement in order to
avoid the detection of the wall support by NO TOUCH detector. In this zone, the safety edge will only be activated from
mechanical compression.
Inhibition zone length depends on NO TOUCH sensitivity adjustment.
When NO-TOUCH sensor is detecting, an LED on the transmitter is activated. If indicators on the transmitter are
switched off, it is needed to push PROG button on the transmitter to activate during 5 minutes the LED visualization on
the transmitter.
LED indicator on MAGIN detector changes to red color when black magnet passes in front of MAGIN.
Before fixing the black magnet, CAP ACTIVE/CAP T must be programmed at the
receiver
The location of the black magnet indicates the inhibition zone at
closing.