background image

20 

 

 

4.4 

REPO Switch 

      The UPS is equipped with an Emergency Power Off (EPO) switch. The user 

must supply a means of interfacing with the EPO circuit to allow disconnecting 
the UPS input feeder breaker to interrupt all sources of power to the UPS and 
connected equipment to comply with national and local wiring codes and 
regulations. 

 
 
 
 
 

1 2 

1 = REPO+ 
2 = Ground 
Short Pin 1 and Pin 2 to enable the REPO function 

21 

 

 

OPERATION 

 

5.1 

  Turn on the UPS 

 

1. Connect the UPS to the wall receptacle. LCD will display “OFF”, when 

Utility is normal. If there is nothing on the LCD, go to step 3. 

 
2. Press the “On” Switch on the front panel for approximately 3 seconds until   

buzzer sounds, then release the “On” Switch to start the UPS. Both the 
LCD and Utility LED (Green) are lit. The start-up procedure is completed 
and the loads are supplied by the UPS. 

 
3. To cold start the UPS, press the “On” Switch on the front panel for 

approximately 3 seconds until the LCD lights up and buzzer sounds, then 
release the “On” Switch. The UPS starts operating and Battery Backup 
LED (Amber) lights up. The cold start-up procedure is completed and the 
loads are supplied by the UPS. 

 

4. The UPS will run under Backup mode and the buzzer alarms every 2 

seconds in case of blackout or over/under voltage. On the contrary, If Utility 
is back to normal and then the UPS will run under Utility mode and silence 
alarm. 

 

5.2 

  Turn Off the UPS

 

 

1. 

Press the “Off” Switch for at least 3 seconds to turn off the UPS. If you 

press the “Off” Switch less than 3 seconds, the UPS will not execute 
shutdown command due to insufficient pressing time. 

 
2. 

In some occasions, the UPS will shut itself down in case of overload, 

output short-circuited or battery cutoff point reached in the Backup mode. 

 
3. 

The UPS will automatically shut off the output and beep for 5 seconds then 

completely shut itself down. 

 

5.3 

 Plug-in Charge

 

 

1. 

If the Input Power Cord is connected to the wall receptacle properly and 

the utility is normal, the UPS will start charging automatically without 
processing “Turn On” procedure. 

 

2. 

You have to charge for at least 8 hours every 3 months to avoid from 

battery self over-discharge naturally, if the UPS is in an idle condition.

 

Содержание 230V 750VA

Страница 1: ...anel 12 3 10 UPS Rear Panel 13 4 INSTALLATION 18 4 1 Connect Utility and Load 18 4 2 Connect Network Surge protection 19 4 3 Connect Computer Interface Port 19 4 4 REPO Switch 20 5 OPERATION 21 5 1 Turn on the UPS 21 5 2 Turn Off the UPS 21 5 3 Plug in Charge 21 5 4 Auto Restart 22 5 5 Alarm Silence 22 5 6 Self Test 22 6 UPS MAINTENANCE 23 6 1 Battery Replacement 23 6 2 How to Replace Battery 24 6...

Страница 2: ...units up to 3KVA are supplied with input cables and output sockets as standard z Plug and play USB RS232 interface conveniently offers a plug and play USB or RS232 port for connecting with nowadays IT products 3 2 IMPORTANT SAFETY INSTRUCTION 2 1 An Important Notice 1 The UPS has its own internal energy source battery Should the battery be switched on when no AC power is available there could be v...

Страница 3: ...f the output is not cut completely 18 SAVE THESE INSTRUCTIONS This Manual Contains Important Instructions that should be followed during Installation and Maintenance of the UPS 19 Symbol for ON Off is displayed and defined 20 Intended for installation in a temperature controlled indoor area free of conductive contaminants 21 Maximum ambient temperature 40 or 0 40 for ambient Operating 2 2 Storage ...

Страница 4: ...e instructions below 1 Keep at least 20cm 8 inches clearance from the rear panel of the UPS from the wall or other obstructions 2 Do not block the air flow to the ventilation openings of the unit 3 Please ensure the installation site environmental conditions are in accordance with the UPS working specifications to avoid overheat and excessive moisture 4 Do not place the UPS in a dusty or corrosive...

Страница 5: ...8 3 6 Tower Setup Stand alone unit 9 3 7 Rack Mount Setup Step1 Step2 ...

Страница 6: ...10 Step3 Step4 Step5 11 3 8 UPS Front Panel ...

Страница 7: ...or or Ground Fault 13 Overload 14 Load Battery Level 15 Load Battery Level Indication Control Button 13 3 10 UPS Rear Panel 1000 1500VA 120V Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 6 1 NEMA 5 15R Output Receptacles 7 Cooling Fan 8 12A Input Circuit Breaker 1000 model only 15A Input Circuit Breaker 1500 model only 9 NEMA 5 15P Input Power ...

Страница 8: ...g Vents 8 30A Input Circuit Breaker 9 NEMA 5 20P Input Power Core 10 REPO 11 Intellislot Port 15 3000VA 120V Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 15A Output Circuit Breaker for 6 1 5 2 20A Output Circuit Breaker for 6 2 6 1 NEMA 5 15R Output Receptacles 6 2 NEMA 5 20R Output Receptacles 6 3 NEMA 5 30R Output Receptacles 7 Cooling V...

Страница 9: ...0 C14 Input Socket 10 REPO 11 Intellislot Port 17 2200 3000VA 230V Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 10A Output Circuit Breaker for 6 1 5 2 10A Output Circuit Breaker for 6 2 6 1 IEC 320 C13 Output Receptacles 6 2 IEC 320 C13 Output Receptacles 6 3 IEC 320 C19 Output Receptacles 7 Cooling Vents 8 15A Input Circuit Breaker 2200 m...

Страница 10: ...ndow Caution Do not connect a laser printer to the UPS outlets 19 4 2 Connect Network Surge protection Connect a 10 base T 100 base T network cable with the RJ 45 network surge protection IN jack on the rear of the UPS Connect from the OUT jack with network cabling to network equipment 4 3 Connect Computer Interface Port Connect the supplied interface cable RS 232 or USB Optional between the inter...

Страница 11: ...ch The UPS starts operating and Battery Backup LED Amber lights up The cold start up procedure is completed and the loads are supplied by the UPS 4 The UPS will run under Backup mode and the buzzer alarms every 2 seconds in case of blackout or over under voltage On the contrary If Utility is back to normal and then the UPS will run under Utility mode and silence alarm 5 2 Turn Off the UPS 1 Press ...

Страница 12: ...n though the Input Power Cord is connected to the wall receptacle Important Notice Plug the UPS onto the wall receptacle to charge the UPS for over 8 hours after initial installation Storage Store at 15 to 30 C 5 to 86 F charge the UPS battery every six months Store at 30 to 45 C 86 to 113 F charge the UPS battery every three months 23 6 UPS MAINTENANCE 6 1 Battery Replacement When the UPS is star...

Страница 13: ...24 6 2 How to Replace Battery STEP 1 STEP 2 25 STEP 3 STEP 4 1000 1500VA ...

Страница 14: ...a DB 9 9 pin female connector on the rear to allow UPS status communications with a computer running UPS software The connection provides serial communication On Battery and Low Battery signals Table 4 DB 9 pin assignment DB 9 Pin Assignment Description 1 Low Battery open collector 2 UPS TxD 3 UPS RxD 4 N C 5 Common 6 N C 7 Low Battery open emitter 8 Utility Fail open emitter 9 Utility Fail open c...

Страница 15: ...h relay contact is 40Vdc 25mA 8 1 4 Installation Position Optional Slot 8 1 5 Flexible signal output for N C Normal Close or N O Normal Open contact by shorting pin1 2 or pin2 3 form JP1 5 8 1 6 The shutdown function will be enabled in 1 minute after blackout occurs if the pin1 2 of both CN1 and CN6 are shorted by cap Or the shutdown function can only be enabled by pin9 10 of CN3 if the pin2 3 of ...

Страница 16: ... after 10 minutes Normal Mode 120 Shutdown UPS immediately 100 119 Continuous Overload Alarm till end of battery discharged 120 130 Shutdown after 10 seconds Battery Mode 130 Shutdown UPS immediately Battery Parameters Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 3x36x7 3x36x9 6x72x7 6x72x9 31 Backup Time Full Load 3 14 2 33 2 41 2 32 Half Load 10 31 8 18 8 40 8 14 Recha...

Страница 17: ...0 109 Continuous Overload Alarm and power to the load 110 120 Shutdown after 10 minutes Normal Mode 120 Shutdown UPS immediately 100 119 Continuous Overload Alarm till end of battery discharged 120 130 Shutdown after 10 seconds Battery Mode 130 Shutdown UPS immediately Battery Parameters Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 2x24x7 3x36x7 3x36x9 6x72x7 6x72x9 Back...

Страница 18: ...34 35 192321372001003 ...

Отзывы: