Tracing start
Tracing start is application for start after fault reset or instantaneous power
failure
.
Using tracing start function
,
inverter can automatically detect the rotation
speed and rotation direction of motor
,
the output the starting frequency and
voltage accordingly
.
Attention
:
when inverter starts in tracing start mode
,
inverter will have speed
tracing in the sequence of high to low frequency
.
High current is likely in start
,
it is also possible to cause current
.
Therefore
,
you
need to have over current level setup
(
P409 setup
).
The specific value depends on the load
In addition
,
when the value of P409 is too low
,
it may lead to a long start time
.
If
over current in the speed tracing
,
inverter will pause the speed tracing
.
P201
Stop mode selection
Setting
Range
:
0
-
1
Unit
:
1
Explanation
:
0
:
Deceleration to stop
1
:
Coasting stop
You can choose a suitable stop mode according to the actual load
.
0
:
Deceleration to stop
Once inverter receives stop command
,
it will reduce the output frequency
according to the deceleration time
.
Factory Setting
:
0
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul
Содержание FC100 Series
Страница 9: ...9 Chapter 2 Storage and Installation ...
Страница 12: ...12 ...
Страница 13: ...13 Chapter 3 Wiring Diagram and Terminal Explanation ...
Страница 20: ...20 ...
Страница 21: ...21 Chapter 4 Keypad Operation ...
Страница 24: ...24 4 ...
Страница 25: ...25 Chapter 5 Function Parameters Table ...
Страница 36: ...36 ...
Страница 37: ...37 Chapter 6 DESCRIPTION OF PARAMETER SETTINGS ...
Страница 99: ...Chapter 7 Maintence and Inspection 99 ...
Страница 108: ...Noise reduction examples 8 108 Chapter 8 Troubleshooting and Fault Informatin FC100 Series User Manaul ...