65
UMG 104
Inputs and outputs
2 digital inputs
Pulse input (S0)
Maximum counting frequency
: 20 Hz
Switching input
Response time (Jasic program)
: 200 ms
Input signal applied
: 18V. 28 V DC (typically 4 mA)
Input signal not applied
: 0 .. 5 V DC, current less than 0.5 mA
2 digital outputs, semi-conductor relay, not short-circuit proof.
Switching voltage
: max 60 V DC, 30 V AC
Switching current
: max 50 mAeff AC/DC
Response time (Jasic program)
: 200 ms
Output of voltage dips
: 20 ms
Output of voltage overranges
: 20 ms
Pulse output (operating pulses)
: max 20 Hz
Cable length
: up to 30 m unshielded
: greater than 30m shielded
Connectable conductors
Solid core, multi-core, flexible core
: 0.08 - 1.5 mm2
Pin-end connector, wire end ferrules
: 1 mm2, only one conductor may connected per
terminal connection!