Shielding
A twisted-conductor and shielded cable must
be provided for connections via the RS485
interface. The shielding at both ends of the
cable must be connected to a large area of
the mounting plate or cabinet parts in order to
achieve an adequate shielding effect.
Cable type
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (Lapp cables)
Unitronic BUS L2/FIP 1x2x0.64 (Lapp cables)
Cable length
1200 m for a baud rate of 38.4 k
Important!
Profibus, RS232, RS485 and
temperature measurement input are
not metallically separated from each
other.
For the wiring of the Modbus con-
nection, CAT cables are not suit-
able. Please use the recommended
cables.