28
UMG 104
Direct measurement
Nominal currents up to 5 A can also be
measured directly with the UMG104.
In this case it must be noted that each
current measurement input may be loaded
continuously with 6 A or for 1 second with max
100 A.
As the UMG104 does not have any integrated
protection for the current measurement,
this protection must be provided for during
installation.
Fig. 28.1 Example, direct current measure-
ment.