34
UMG 104
RS485 Bus
A
B
A
B
RS485
Bus structure
All devices are connected in a bus structure
(line). Up to 32 stations can be connected
together in a segment. The cable at the start
and end of a segment is terminated with
resistors.
If there are more than 32 stations, repeaters
must be used to connect the individual
segments.
Correct
Incorrect
Terminal strip in the control cabinet.
Device with RS485 interface.
(Without terminating resistor)
Device with RS485 interface.
(With terminating resistor at the device)
Terminating resistors
The cable at the start and end of a segment is
terminated with resistors (120 ohm, 1/4 W).
The UMG104 does not contain any terminating
resistors.
B
A
Содержание UMG 104
Страница 69: ...69 UMG 104...
Страница 78: ...78 UMG 104 Dimensioned drawings Front view Side view...