Module 96-PA-RCM / 96-PA-RCM-EL
www.janitza.de
42
9. Module-relevant configuration
Configure the relevant parameters for the module
in the
Measurement
window of your basic device
with module. To do so, use the function buttons
of the basic device to go to the
Measurement
window
:
·Press button 1 (
Menu
) until the menu is open
.
·Use buttons 3/4 (
“
”/“
”
) to select the menu
item
Configuration
and confirm with button 6
Enter.
·In the
Configuration
window, use buttons 3/4
(
“
”/“
”
) to select the item
Measurement
and
confirm with button 6
Enter
.
·The
Measurement
window appears with the
following
settings for the RCM module
:
A.
Transformer for the basic device (I1 to I3)
and L4 current transformer (I4 - neutral
conductor measurement).
B.
Transformer for the module mode
Residual current
or
DC power
.
C.
Temperature sensor.
9.1 L4 current transformer (I4 - measure-
ment)
The
Transformer
item allows configuration of the
current and voltage transformer ratios of the basic
device as well as the current transformer ratios for
the L4 current measurement (e.g. neutral conduc-
tor measurement).
1. Use buttons 3/4 (
“
”/“
”
) to select the item
Transformer
and confirm with button 6
Enter.
2. The Window for configuration of the L4 (I4)
current transformer appears.
3. Select the item
L4 (I4) current transformer
and
confirm with button 6
Enter
.
4. Use the function buttons of the basic device
to configure the current transformer ratio as
described in chap. „7. Operation and button
functions of the basic device with module“ on
page 35.
A
B
C
Fig. Window Measurement with the settings for the
RCM module
Fig. Window Measurement with the L4 current transformer
for the RCM module (default setting 5 / 5 A).
A
INFORMATION
You can also set the module-relevant configura-
tion in the GridVis
®
power grid monitoring soft-
ware, see section„9.5 Module-relevant configura-
tion with the GridVis® software“ on page 46.