8. Communication
8.1 Basic device communication via the
Ethernet interface (module 96-PA-RCM-
EL)
The basic device with module 96-PA-RCM-EL
has six ways to allocate addresses for an Ethernet
connection (TCP/IP):
1. Static
The user selects the IP address, netmask and
gateway on the device. Use this mode for sim-
ple networks with no DHCP server.
2. BOOTP
Automatically integrates your device in an exist-
ing network. BOOTP is an older protocol and
has a smaller range of functions than DHCP.
3. DHCP
On start-up, the device is automatically given
an IP address, netmask and gateway from the
DHCP server.
4. Static gratuitous ARP
The user selects the IP address, netmask and
gateway on the device. The device automat-
ically logs into the network with IP and MAC
address.
5. BOOTP ARP Probe
Simplified protocol for the automatic assign-
ment of IP addresses to the MAC addresses.
The device automatically logs into the network
with IP and MAC address.
6. DHCP ARP Probe
Protocol for the automatic assignment of IP
addresses to the MAC addresses. The device
automatically logs into the network with IP and
MAC address.
Fig. Window Communication > Ethernet configuration
8.1.1 Configuring Ethernet settings on the
basic device
Configure the Ethernet settings or obtain details
from the window
Communication > Ethernet
(TCP/IP)
:
·Press button 1 (
Menu
) until the menu is open
.
·Use the buttons 3/4 (
"
"/"
"
)
to select the
menu item
Configuration
and
confirm with
button 6
Enter
.
·In the
Configuration
window, use button 3 or 4
to select the item
Communication
and confirm
with key 6.
·In the
Communication
window, use button 3
or 4 to select the item
Ethernet Config
and
confirm with button 6.
·The window
Communication
appears with the
Ethernet settings:
·Configure the Ethernet (TCP/IP) settings as
specified by the network administrator.
Information on basic operation can be found in
section „7. Operation and button functions of the
basic device with module“ on page 35.
INFORMATION
·
The standard factory setting of the basic de-
vice with module 96-PA-RCM-EL is “dynamic
assignment of IP address” (DHCP mode).
·