background image

Page 4

1.   Remove the vent exhaust grille by removing 

the four screws which retain it. The grille, its 
gasket, and the screws may be discarded.

2.   Place the vent collar gasket on the top of 

the heater aligning its center hole and screw 
holes with those in the top of the heater.

3.   Place the vent collar over the gasket and 

fasten it in place with the screws and 
lockwashers provided. Be sure that all 
components are properly aligned. Screws 
must be tightened enough to assure a sealed 
joint without deforming the vent collar.

2G-2. Combustion Air Requirements for 

One-Pipe Installation

One-pipe indoor installations must have specifi c 

provisions for supply of combustion and ventilation 
air to the room in which the heater is located. Two air 
openings must be provided — one near the ceiling 
and one near the fl oor. When air is provided directly 
through an outside wall, each opening must have at 
least one square inch (6.5 square cm) of area per 4000 

Figure 4. Vent collar assembly for indoor installation.

BTU/h of heater input. When air is provided indirectly 
through ducts from the outside, the openings and 
passages must have at least one square inch of area 
per 2000 Btu/h of heater input. These requirements are 
interpreted in Table 2.

Table 2. Required Net Free Area of Openings for 
Combustion and Ventilation Air.

Note that the numbers indicate the 

net free area

— after allowing for the blockage of grille bars, etc. 
See applicable local codes and the previously-cited 
national codes for details. Even though codes may 
permit it, Jandy does not recommend installations 
with only “infi ltration” as the means for provision of 
combustion air.

See Section 2G-3c for vent pipe sizing.

WARNING

Do not store any chemicals, cleaners, or other cor-
rosive material near combustion air openings or in 
the room. Avoid location of dryer vents in the vicinity 
of combustion air openings. Failure to prevent cor-
rosive materials from mixing with combustion air 
can result in reduced heater life and unsafe heater 
operation.

2G-3. Two-Pipe Installation (Direct Vent)

This section specifi es installation requirements 

for combustion air and vent piping for “two pipe” 
installations. A two-pipe system provides isolation of 
the Hi-E

2

 combustion system from the space in which 

the heater is installed. It has not only a vent pipe, 
but also a combustion air pipe to provide air directly 
from the outdoors. Research studies have shown that 
contaminants which may corrode internal heater parts 
are typically at much lower levels in outdoor air than 
in air from indoors.

2G-3a. Connection of Combustion Air 

Pipe

A collar for combustion air pipe connection is 

provided in the heater at the inlet of the fi lter box. 
As shown in Figure 5, the combustion air pipe is 
routed through the side of the heater to the fi lter box 
connection. Remove the cover plate from the left side 
panel to provide access for the air pipe.

Figure 3. Removal of outdoor exhaust grille.

Model

Required net free area in square 

inches (sq. cm) for each of 2 openings 

- one near ceiling and one near fl oor

Directly Through 

an Exterior Wall

Through Horizon-

tal Ducts

220

55 (355)

110 (710)

350

88 (570)

175 (1130)

Содержание Hi-E2 EHe

Страница 1: ...0D Installation and Operating Data WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline o...

Страница 2: ...perature Controls 17 3C Lighting and Shutdown 17 3C 1 Lighting the Heater 17 3C 2 Shutdown 17 3D Water Chemistry 18 3D 1 Pools 18 3D 2 Spas 18 3D 2a Spa Water Chemistry 18 3D 2b Water Changing 18 3D 2...

Страница 3: ...his manual The home owner should fill out the warranty registration card included in the plastic bag and return it via mail The warranty does not cover damage caused by improper installation operation...

Страница 4: ...equipment is located below the pool sur face a leak from any component can cause large scale water loss or flooding Jandy Pool Products Inc cannot be responsible for such water loss or flooding or re...

Страница 5: ...ed within the heater The conversion can be done quite simply as follows see Figures 3 and 4 Figure 1 Outdoor heater location If the heater is installed close to a structure protect it from rain water...

Страница 6: ...national codes for details Even though codes may permit it Jandy does not recommend installations with only infiltration as the means for provision of combustion air See Section 2G 3c for vent pipe si...

Страница 7: ...ength of pipe determine how much it restricts flow to or from the heater Also a large heater requires larger pipe than a small heater because it operates with higher flow of combustion air and exhaust...

Страница 8: ...vent exhaust does not settle on building surfaces and other nearby objects Vent products may corrode such surfaces or objects 3 Locate the vent terminal at a sufficient horizontal distance from any ga...

Страница 9: ...2 releases heat to its environment and a room with no ventilation may become too warm In one pipe installations the normal code required provisions for combustion air also assure reasonable ventilatio...

Страница 10: ...stone pebble does not plug any of the tubes Place the cover on the tray when this is done It is important that there be no sagging sections of tubing to trap water Drainage to the trap and out of the...

Страница 11: ...eral operation gas appliances are normally de rated when installed at high elevation This is not necessary with the Hi E2 because it has a special venturi type combustion system which self compensates...

Страница 12: ...Page 10 Figure 17 Typical time clock wiring Figure 16 Wiring diagram Hi E2 pool heater Figure 18 Terminal block for fireman s switch or remote control wiring...

Страница 13: ...installation Wiring should include a means to prevent operation of the heater when there is no water flow This is typically done with a time clock Fireman s Switch as discussed in Section 2J 3 2J 2 Bo...

Страница 14: ...re no more than six feet below the pool water surface and no more than 15 feet above it See instructions for pressure switch adjustment in the heater start up section of this manual for more informati...

Страница 15: ...n be connected directly to the heater using the rubber donut gaskets provided with the heater 2 PVC or metal pipe can be threaded directly to the flanges and 1 1 2 schedule 40 metal pipe can be used w...

Страница 16: ...gas valve This regulator is factory set between 1 25 and 3 0 WC regardless of whether natural or LP gas is used by the heater The step down regulator does not change operate the heater If the recomme...

Страница 17: ...y rotating the adjuster counterclockwise as far as it will go 2 Start the filter pump and confirm by means of an ohmmeter that the pressure switch closes if the switch fails to close replace it with a...

Страница 18: ...face of the header and install a pocket thermometer see Figure 25 Proceed as follows 1 If the piping system has a manual bypass valve close it 2 Turn off the heater by moving the Flex Temp switch on t...

Страница 19: ...all time clock settings This lets the filter system and heater operate continuously until the water reaches the temperature setting on the thermostat When that happens the heater will shut off automat...

Страница 20: ...during heavy usage Be sure to stabilize the water chemistry after every water change 3D 2c Corrosion The corrosive action of pool spa water is increased by the following 1 Low pH acidity 2 Low Total...

Страница 21: ...dy temperature of 98 6 F 37 C Symptoms include dizziness fainting drowsiness lethargy and an increase in the internal body temperature The effects of hyperthermia include Unawareness of impending haza...

Страница 22: ...air filter 3 For heaters installed with combustion air or vent piping inspect screens at the inlet or outlet of these pipes Clean screens as necessary to assure free flow see illustrations in combust...

Страница 23: ...means of a thermistor and controls heater operation to bring the water to that selected It has two temperature setting knobs which are typically used to set pool and spa temperatures A selector switch...

Страница 24: ...t exchanger If the pool water pump fails or the water filter is blocked the pressure switch prevents operation of the burner It can be affected by the installation conditions as discussed earlier in t...

Страница 25: ...is no voltage inspect the rest of the wiring to be sure that there is no short such as contact of a terminal with the heater chassis or another terminal Correct any such condition and replace the fus...

Страница 26: ...lace a defective limit switch Limit switch access is through the side cover panel on the side of the heater to which water pipes are connected Note that the limit switches have different trip points a...

Страница 27: ...specially that propane gas is not being provided to a heater configured for natural gas To confirm correction of the Adjustment of Pressure Switch If there is no problem with the pool system or pressu...

Страница 28: ...hot even when the component is not operating 4E 2k Combustion Blower The combustion blower operates when it is provided with 115V 60 Hz power Confirm this by connecting the voltmeter between the neut...

Страница 29: ...e side of the manometer to the outlet pressure port of the gas valve See Figure 35 Turn the heater on Until the heater fires the manometer will indicate several inches of water pressure but after the...

Страница 30: ...offset is correctly set but gas orifice differential is abnormal check air flow through the system per the following sections 4F 3a Unfired Venturi Differential Pres sure Determine if air flow throug...

Страница 31: ...Venturi Ft m Differential Differential Sea Level 4 0 102 mm WC 4 7 119 mm WC 2000 610 3 7 94 4 3 109 4000 1220 3 4 86 4 0 102 6000 1830 3 2 81 3 7 94 8000 2440 2 9 74 3 5 89 10000 3050 2 7 69 3 2 81 T...

Страница 32: ...placement packages are available from Jandy or its representatives It is normal that a blue green deposit forms in the neutralizer This is caused by very small concentrations of copper ions present in...

Страница 33: ...ight 220 225 8 220 000 206 lbs 350 317 8 350 000 252 lbs SECTION 6 Replacement Parts 6A Parts List To order or purchase parts for the Jandy Hi E2 pool spa heater contact your nearest dealer or distrib...

Страница 34: ...lamp All R0308800 55 Vent Duct Assembly All R0303100 56 Vent Duct Heater Top Gasket or All R0309100 Heater Top Indoor Vent Collar Gasket 57 Heater Top Outdoor All R0309500 Exhaust Grille Gasket 58 Out...

Страница 35: ...ed View of the Hi E2 10 6 7 1 2 5 8 9 43 47 67 68 55 52 41 12 60 62 51 50 30 46 45 3 24 29 18 23 70 72 77 83 31 66 74 76 13 4 14 15 17 35 36 37 38 39 40 42 44 16 49 56 57 58 65 69 85 86 88 87 89 53 54...

Страница 36: ...nts insects negligence or acts of God 5 Scaling freezing or other conditions causing inadequate water circulation 6 Operating the product s at water flow rates outside the published minimum and maximu...

Отзывы: