background image

Hi-E2

Page 15

requirements for gas supply piping or pressure, and it 
does not change servicing procedures for the venturi/
combination fl ow system. Gas supply must be as 
stated in the installation and operation manual and on 
the heater rating plate. Servicing procedures for the 
venturi/combustion fl ow system must be as specifi ed 
in the installation and operation manual. Incorrect 
adjustment of the combination gas control can cause 
improper heater operation and hazardous combustion 
emissions.

If it is necessary 

to verify adjustment 
of the step-down 
regulator, its outlet 
pressure can be 
measured at the inlet 
tap of the combination 
gas valve, which is 
immediately to the 
right of the step-down 
regulator.

To order this 

regulator as a separate 
part, please order kit number R0337300.

2L-5. Adjustment of Water Pressure  

Switch

The pressure switch is pre-set at the factory for 

normal pool installations. Do not adjust it unless the 
heater water connections are more than three feet 
above or below the pool surface. If they are not in this 
range, the pressure switch must be adjusted. This can 
be done in the fi eld if the water connections are no 
more than six feet above the pool surface and no more 
than ten feet below it. For other situations, contact a 
Jandy representative.

 Caution

The pressure switch should be adjusted to turn the 
heater off when the pump is off. Setting the switch 
to close at too low of a fl ow can damage the appli-
ance.

To adjust the pressure switch, proceed as follows 

(see Figure 24).

The pool fi lter must be clean before making this 

adjustment. The heater does not have to be fi ring.

1.   Turn the Flex Temp switch to OFF, and 

make sure the pressure switch is at its lowest 
setting. This is done by rotating the adjuster 
counterclockwise as far as it will go.

2.   Start the fi lter pump and confi rm by means of 

an ohmmeter that the pressure switch closes 
(if the switch fails to close, replace it with a 
switch which has a lower minimum setting).

3.   Turn Flex Temp switch to ON. Heater should 

start.

4.   Pry out the top rubber dirt plug.

5.   Use a 7/32 inch Allen wrench to turn the 

adjustment screw very slowly clockwise until 
the heater goes off.

6.   Slowly turn the pressure switch adjustment 

screw

counter-clockwise

 one-quarter turn. 

The heater should come back on

7.   Check the adjustment by turning the fi lter 

pump OFF. The heater should shut off 
immediately. If it does not, restart the fi lter 
pump and repeat Steps 6 and 7. Check the 
adjustment again.

8.   Return the pool temperature control to the 

desired temperature.

It may be necessary to repeat these steps to get 

a proper setting. The switch must be set so that the 
heater will not fi re unless the pump is running. If a 
proper setting cannot be reached, contact the factory 
service department.

2L-6. Water Temperature Rise

The Hi-E

2

 pool heater has an internal bypass 

device which accommodates a wide range of water 
fl ow. Its purpose is to assure that fl ow through the 
heat exchanger is adequate to provide high effi ciency 
operation and prevent overheating even though fl ow 
through the fi lter system may vary.

Correct water fl ow should be confi rmed upon 

start-up of the heater and in most servicing situations. 
If fl ow is not normal, corrections must be made to 
the pool system. If the system has an external fl ow 
bypass (because of very high fi lter system fl ow), it 
should be adjusted to provide proper fl ow through the 
heater. Flow is evaluated by determining the water 
temperature rise through the heat exchanger.

Before checking temperature rise, be sure the 

pool fi lter is clean. If necessary, clean the fi lter. 

Figure 24. Adjustment of pressure switch.

Pry off cap

to adjust

Содержание Hi-E2 EHe

Страница 1: ...0D Installation and Operating Data WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline o...

Страница 2: ...perature Controls 17 3C Lighting and Shutdown 17 3C 1 Lighting the Heater 17 3C 2 Shutdown 17 3D Water Chemistry 18 3D 1 Pools 18 3D 2 Spas 18 3D 2a Spa Water Chemistry 18 3D 2b Water Changing 18 3D 2...

Страница 3: ...his manual The home owner should fill out the warranty registration card included in the plastic bag and return it via mail The warranty does not cover damage caused by improper installation operation...

Страница 4: ...equipment is located below the pool sur face a leak from any component can cause large scale water loss or flooding Jandy Pool Products Inc cannot be responsible for such water loss or flooding or re...

Страница 5: ...ed within the heater The conversion can be done quite simply as follows see Figures 3 and 4 Figure 1 Outdoor heater location If the heater is installed close to a structure protect it from rain water...

Страница 6: ...national codes for details Even though codes may permit it Jandy does not recommend installations with only infiltration as the means for provision of combustion air See Section 2G 3c for vent pipe si...

Страница 7: ...ength of pipe determine how much it restricts flow to or from the heater Also a large heater requires larger pipe than a small heater because it operates with higher flow of combustion air and exhaust...

Страница 8: ...vent exhaust does not settle on building surfaces and other nearby objects Vent products may corrode such surfaces or objects 3 Locate the vent terminal at a sufficient horizontal distance from any ga...

Страница 9: ...2 releases heat to its environment and a room with no ventilation may become too warm In one pipe installations the normal code required provisions for combustion air also assure reasonable ventilatio...

Страница 10: ...stone pebble does not plug any of the tubes Place the cover on the tray when this is done It is important that there be no sagging sections of tubing to trap water Drainage to the trap and out of the...

Страница 11: ...eral operation gas appliances are normally de rated when installed at high elevation This is not necessary with the Hi E2 because it has a special venturi type combustion system which self compensates...

Страница 12: ...Page 10 Figure 17 Typical time clock wiring Figure 16 Wiring diagram Hi E2 pool heater Figure 18 Terminal block for fireman s switch or remote control wiring...

Страница 13: ...installation Wiring should include a means to prevent operation of the heater when there is no water flow This is typically done with a time clock Fireman s Switch as discussed in Section 2J 3 2J 2 Bo...

Страница 14: ...re no more than six feet below the pool water surface and no more than 15 feet above it See instructions for pressure switch adjustment in the heater start up section of this manual for more informati...

Страница 15: ...n be connected directly to the heater using the rubber donut gaskets provided with the heater 2 PVC or metal pipe can be threaded directly to the flanges and 1 1 2 schedule 40 metal pipe can be used w...

Страница 16: ...gas valve This regulator is factory set between 1 25 and 3 0 WC regardless of whether natural or LP gas is used by the heater The step down regulator does not change operate the heater If the recomme...

Страница 17: ...y rotating the adjuster counterclockwise as far as it will go 2 Start the filter pump and confirm by means of an ohmmeter that the pressure switch closes if the switch fails to close replace it with a...

Страница 18: ...face of the header and install a pocket thermometer see Figure 25 Proceed as follows 1 If the piping system has a manual bypass valve close it 2 Turn off the heater by moving the Flex Temp switch on t...

Страница 19: ...all time clock settings This lets the filter system and heater operate continuously until the water reaches the temperature setting on the thermostat When that happens the heater will shut off automat...

Страница 20: ...during heavy usage Be sure to stabilize the water chemistry after every water change 3D 2c Corrosion The corrosive action of pool spa water is increased by the following 1 Low pH acidity 2 Low Total...

Страница 21: ...dy temperature of 98 6 F 37 C Symptoms include dizziness fainting drowsiness lethargy and an increase in the internal body temperature The effects of hyperthermia include Unawareness of impending haza...

Страница 22: ...air filter 3 For heaters installed with combustion air or vent piping inspect screens at the inlet or outlet of these pipes Clean screens as necessary to assure free flow see illustrations in combust...

Страница 23: ...means of a thermistor and controls heater operation to bring the water to that selected It has two temperature setting knobs which are typically used to set pool and spa temperatures A selector switch...

Страница 24: ...t exchanger If the pool water pump fails or the water filter is blocked the pressure switch prevents operation of the burner It can be affected by the installation conditions as discussed earlier in t...

Страница 25: ...is no voltage inspect the rest of the wiring to be sure that there is no short such as contact of a terminal with the heater chassis or another terminal Correct any such condition and replace the fus...

Страница 26: ...lace a defective limit switch Limit switch access is through the side cover panel on the side of the heater to which water pipes are connected Note that the limit switches have different trip points a...

Страница 27: ...specially that propane gas is not being provided to a heater configured for natural gas To confirm correction of the Adjustment of Pressure Switch If there is no problem with the pool system or pressu...

Страница 28: ...hot even when the component is not operating 4E 2k Combustion Blower The combustion blower operates when it is provided with 115V 60 Hz power Confirm this by connecting the voltmeter between the neut...

Страница 29: ...e side of the manometer to the outlet pressure port of the gas valve See Figure 35 Turn the heater on Until the heater fires the manometer will indicate several inches of water pressure but after the...

Страница 30: ...offset is correctly set but gas orifice differential is abnormal check air flow through the system per the following sections 4F 3a Unfired Venturi Differential Pres sure Determine if air flow throug...

Страница 31: ...Venturi Ft m Differential Differential Sea Level 4 0 102 mm WC 4 7 119 mm WC 2000 610 3 7 94 4 3 109 4000 1220 3 4 86 4 0 102 6000 1830 3 2 81 3 7 94 8000 2440 2 9 74 3 5 89 10000 3050 2 7 69 3 2 81 T...

Страница 32: ...placement packages are available from Jandy or its representatives It is normal that a blue green deposit forms in the neutralizer This is caused by very small concentrations of copper ions present in...

Страница 33: ...ight 220 225 8 220 000 206 lbs 350 317 8 350 000 252 lbs SECTION 6 Replacement Parts 6A Parts List To order or purchase parts for the Jandy Hi E2 pool spa heater contact your nearest dealer or distrib...

Страница 34: ...lamp All R0308800 55 Vent Duct Assembly All R0303100 56 Vent Duct Heater Top Gasket or All R0309100 Heater Top Indoor Vent Collar Gasket 57 Heater Top Outdoor All R0309500 Exhaust Grille Gasket 58 Out...

Страница 35: ...ed View of the Hi E2 10 6 7 1 2 5 8 9 43 47 67 68 55 52 41 12 60 62 51 50 30 46 45 3 24 29 18 23 70 72 77 83 31 66 74 76 13 4 14 15 17 35 36 37 38 39 40 42 44 16 49 56 57 58 65 69 85 86 88 87 89 53 54...

Страница 36: ...nts insects negligence or acts of God 5 Scaling freezing or other conditions causing inadequate water circulation 6 Operating the product s at water flow rates outside the published minimum and maximu...

Отзывы: