Jandy Hi-E2 EHe Скачать руководство пользователя страница 30

Page 28

cut short if necessary) can be used.  Insert the screw 
driver through the hole on the motor housing.  Turn it 
clockwise to increase the fl ow and counter-clockwise 
to decrease.

If blower speed adjustment results in acceptable 

venturi differential, shut off the system at the Flex-
Temp control and return to “Gas orifi ce differential” 
measurement per Section 4F-2b.  Make a fi nal speed 
adjustment

as necessary to obtain correct gas orifi ce 

differential.

If the system cannot be made to operate normally 

by blower speed adjustment, investigate possible fl ow 
problems per the following sections.

4F-3b. Combustion Air Flow

Begin by connecting the 

negative

 side of 

the manometer to the venturi inlet and leaving the 

positive

 side open to ambient, as shown in Figure 

39. In a normally operating heater, the pressure will 
be 0.2 to 0.6" WC 

less

 than the ambient pressure.

The reading for a model 220 with clean fi lter and 
no combustion air duct will be near the low end of 
this range. For a model 350 with clean fi lter and no 
combustion air duct, the reading will be near the 
middle. If combustion air is ducted to the heater, the 
reading will be near the high end. If an excessive 
reading is observed (i.e. 

more negative

), fl ow is 

probably restricted by a dirty fi lter or blockage in 
the combustion air supply system. Correct any such 
problems and verify normal operation by returning to 
the venturi system checkout procedures. 

Pressure readings will be less if the heater is 

located at an elevation signifi cantly above sea level.

4F-3c. Flow in Heater and Vent

If the venturi inlet pressure reading is normal 

(or less than normal), fl ow may be blocked within the 

4F-3. Air Flow Investigation

If gas pressure offset is correctly set but gas 

orifi ce differential is abnormal, check air fl ow through 
the system per the following sections.

4F-3a. Unfi red Venturi Differential Pres-

sure.

Determine if air fl ow through the system is in 

a normal range by operating the system with the gas 
valve turned off.  Connect the positive side of the 
manometer to the venturi inlet port, which is at the 
bottom on the right side. Connect the negative side 
of the manometer to the outlet pressure port of the 
gas valve (see Figure 37). Turn the gas valve knob to 
"Off". Turn the heater on by selecting "Pool" or "Spa" 
at the Flex Temp control and adjusting the temperature 
setting high. The blower will start immediately and 
the manometer will indicate the "unfi red venturi 
differential" pressure. This is the pressure difference 
created by airfl ow through the venturi. It should be 
approximately 4.7" ± 0.3" at sea level. (See Section 
4F-5 for other elevations.)

Note that when the heater is operated with the 

gas valve off, it will eventually “lock out” because the 
ignition control does not sense fl ame.  Normally there 
will be enough time to obtain the measurement, but if 
necessary, additional blower operation can be induced 
by turning the Flex-Temp control off and then back on 
again.

If the reading is not normal, attempt to correct it 

by blower speed adjustment.  Blower speed is adjusted 
by turning a special screw on the right side of the 
motor - at about 4 O’clock.  (See Figure 38.)  A small 
countersunk hole is provided there for access to the 
screw, but is covered by a thin silver-colored label. 
Remove or puncture the label.

A small fl at-blade screw driver is required.  It 

must have a 3/32” or 2.5 mm (.098”) blade and must 
be about 4-1/2” long.  A jeweler’s screw driver or an 
electronics pot adjustment screw driver (with handle 

SPEED
ADJUSTMENT 
SCREW

Figure 38. Blower Speed Adjustment.

+

-

4.70

Figure 37. Unfi red venturi differential measurement.

Содержание Hi-E2 EHe

Страница 1: ...0D Installation and Operating Data WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline o...

Страница 2: ...perature Controls 17 3C Lighting and Shutdown 17 3C 1 Lighting the Heater 17 3C 2 Shutdown 17 3D Water Chemistry 18 3D 1 Pools 18 3D 2 Spas 18 3D 2a Spa Water Chemistry 18 3D 2b Water Changing 18 3D 2...

Страница 3: ...his manual The home owner should fill out the warranty registration card included in the plastic bag and return it via mail The warranty does not cover damage caused by improper installation operation...

Страница 4: ...equipment is located below the pool sur face a leak from any component can cause large scale water loss or flooding Jandy Pool Products Inc cannot be responsible for such water loss or flooding or re...

Страница 5: ...ed within the heater The conversion can be done quite simply as follows see Figures 3 and 4 Figure 1 Outdoor heater location If the heater is installed close to a structure protect it from rain water...

Страница 6: ...national codes for details Even though codes may permit it Jandy does not recommend installations with only infiltration as the means for provision of combustion air See Section 2G 3c for vent pipe si...

Страница 7: ...ength of pipe determine how much it restricts flow to or from the heater Also a large heater requires larger pipe than a small heater because it operates with higher flow of combustion air and exhaust...

Страница 8: ...vent exhaust does not settle on building surfaces and other nearby objects Vent products may corrode such surfaces or objects 3 Locate the vent terminal at a sufficient horizontal distance from any ga...

Страница 9: ...2 releases heat to its environment and a room with no ventilation may become too warm In one pipe installations the normal code required provisions for combustion air also assure reasonable ventilatio...

Страница 10: ...stone pebble does not plug any of the tubes Place the cover on the tray when this is done It is important that there be no sagging sections of tubing to trap water Drainage to the trap and out of the...

Страница 11: ...eral operation gas appliances are normally de rated when installed at high elevation This is not necessary with the Hi E2 because it has a special venturi type combustion system which self compensates...

Страница 12: ...Page 10 Figure 17 Typical time clock wiring Figure 16 Wiring diagram Hi E2 pool heater Figure 18 Terminal block for fireman s switch or remote control wiring...

Страница 13: ...installation Wiring should include a means to prevent operation of the heater when there is no water flow This is typically done with a time clock Fireman s Switch as discussed in Section 2J 3 2J 2 Bo...

Страница 14: ...re no more than six feet below the pool water surface and no more than 15 feet above it See instructions for pressure switch adjustment in the heater start up section of this manual for more informati...

Страница 15: ...n be connected directly to the heater using the rubber donut gaskets provided with the heater 2 PVC or metal pipe can be threaded directly to the flanges and 1 1 2 schedule 40 metal pipe can be used w...

Страница 16: ...gas valve This regulator is factory set between 1 25 and 3 0 WC regardless of whether natural or LP gas is used by the heater The step down regulator does not change operate the heater If the recomme...

Страница 17: ...y rotating the adjuster counterclockwise as far as it will go 2 Start the filter pump and confirm by means of an ohmmeter that the pressure switch closes if the switch fails to close replace it with a...

Страница 18: ...face of the header and install a pocket thermometer see Figure 25 Proceed as follows 1 If the piping system has a manual bypass valve close it 2 Turn off the heater by moving the Flex Temp switch on t...

Страница 19: ...all time clock settings This lets the filter system and heater operate continuously until the water reaches the temperature setting on the thermostat When that happens the heater will shut off automat...

Страница 20: ...during heavy usage Be sure to stabilize the water chemistry after every water change 3D 2c Corrosion The corrosive action of pool spa water is increased by the following 1 Low pH acidity 2 Low Total...

Страница 21: ...dy temperature of 98 6 F 37 C Symptoms include dizziness fainting drowsiness lethargy and an increase in the internal body temperature The effects of hyperthermia include Unawareness of impending haza...

Страница 22: ...air filter 3 For heaters installed with combustion air or vent piping inspect screens at the inlet or outlet of these pipes Clean screens as necessary to assure free flow see illustrations in combust...

Страница 23: ...means of a thermistor and controls heater operation to bring the water to that selected It has two temperature setting knobs which are typically used to set pool and spa temperatures A selector switch...

Страница 24: ...t exchanger If the pool water pump fails or the water filter is blocked the pressure switch prevents operation of the burner It can be affected by the installation conditions as discussed earlier in t...

Страница 25: ...is no voltage inspect the rest of the wiring to be sure that there is no short such as contact of a terminal with the heater chassis or another terminal Correct any such condition and replace the fus...

Страница 26: ...lace a defective limit switch Limit switch access is through the side cover panel on the side of the heater to which water pipes are connected Note that the limit switches have different trip points a...

Страница 27: ...specially that propane gas is not being provided to a heater configured for natural gas To confirm correction of the Adjustment of Pressure Switch If there is no problem with the pool system or pressu...

Страница 28: ...hot even when the component is not operating 4E 2k Combustion Blower The combustion blower operates when it is provided with 115V 60 Hz power Confirm this by connecting the voltmeter between the neut...

Страница 29: ...e side of the manometer to the outlet pressure port of the gas valve See Figure 35 Turn the heater on Until the heater fires the manometer will indicate several inches of water pressure but after the...

Страница 30: ...offset is correctly set but gas orifice differential is abnormal check air flow through the system per the following sections 4F 3a Unfired Venturi Differential Pres sure Determine if air flow throug...

Страница 31: ...Venturi Ft m Differential Differential Sea Level 4 0 102 mm WC 4 7 119 mm WC 2000 610 3 7 94 4 3 109 4000 1220 3 4 86 4 0 102 6000 1830 3 2 81 3 7 94 8000 2440 2 9 74 3 5 89 10000 3050 2 7 69 3 2 81 T...

Страница 32: ...placement packages are available from Jandy or its representatives It is normal that a blue green deposit forms in the neutralizer This is caused by very small concentrations of copper ions present in...

Страница 33: ...ight 220 225 8 220 000 206 lbs 350 317 8 350 000 252 lbs SECTION 6 Replacement Parts 6A Parts List To order or purchase parts for the Jandy Hi E2 pool spa heater contact your nearest dealer or distrib...

Страница 34: ...lamp All R0308800 55 Vent Duct Assembly All R0303100 56 Vent Duct Heater Top Gasket or All R0309100 Heater Top Indoor Vent Collar Gasket 57 Heater Top Outdoor All R0309500 Exhaust Grille Gasket 58 Out...

Страница 35: ...ed View of the Hi E2 10 6 7 1 2 5 8 9 43 47 67 68 55 52 41 12 60 62 51 50 30 46 45 3 24 29 18 23 70 72 77 83 31 66 74 76 13 4 14 15 17 35 36 37 38 39 40 42 44 16 49 56 57 58 65 69 85 86 88 87 89 53 54...

Страница 36: ...nts insects negligence or acts of God 5 Scaling freezing or other conditions causing inadequate water circulation 6 Operating the product s at water flow rates outside the published minimum and maximu...

Отзывы: