Issue: 01.05.2017
Page 32
Technical Information
SNS Pressure Switch
Safety pressure switch settings:
The pressure switch fitted to condensing units with auto reset for low pressure is factory preset to 1.0
bar cut-out.
Do not set pressure control below this setting.
Setting procedure for SNS Pressure switch:
Turning the range adjusting screw counterclockwise increases the setting pressure. Turning the range
adjusting screw clockwise decreases the setting pressure.
Turning the differential adjusting screw clockwise increases the differential. Turning the differential
adjusting screw anti-clockwise decreases the differential setting.
By turning these two adjusting screws, the desired setting pressure and differential are obtained.
Lock the spindles with the locking plate after setting.
1. Micro Switch
2. Range Adjusting Screw
3. Differential Adjusting
Screw
4. Low Pressure Scale Plate
5. Low Pressure Range Pointer
6. Differential Pointer
7. Low Pressure Bellows Cover