Alarm Information
Alarm Codes
Type of alarm
The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be
displayed on the main screen and the alarm LED will be on or blinking.
Code
Description
Reset type
A01
Clock board error
Auto
A08
Suction temperature probe fault
Auto
A09
Outdoor temperature probe fault
Auto
A10
Condensing coil temperature probe fault
Auto
A11
Discharge temperature probe fault
Auto
A13
Discharge pressure transducer fault
Auto
A14
Suction pressure transducer fault
Auto
A15
Outside of operating envelope (Digital scroll)
Auto
A16
Condensing coil high temperature
Auto
A17
Compressor high discharge temperature alarm
Auto
A19
Compressor overload trip
Auto
A24
Low pressure alarm by transducer
Auto:
A25
High pressure alarm by transducer
Auto: less than 3 times in 30 minutes
Manual: 3 times or more in 30 minutes
A26
Low pressure alarm by pressure switch
Auto
A27
Compressor high pressure alarm by pressure switch
Manual
Alarm LED
Off
No alarm
On
Only auto reset alarm
Blinking
Manual reset alarm
Auto:
An alarm condition is created but when cleared the unit will restart automatically.
Manual:
An alarm condition is created but requires resetting manually before the unit can restart.
To Reset Alarm Condition:
•
Press
ALARM
button for more than 5 seconds.
•
Power controller
OFF
then back
ON
.
Содержание JEHSD-0600-M-3
Страница 27: ...Issue 01 05 2017 Page 27 Drawings Dimensional drawing JEHSD 0600 M 3 ...
Страница 28: ...Issue 01 05 2017 Page 28 Drawings Electrical Wiring Diagram JEHSD 0600 M 3 ...
Страница 34: ...Issue 01 05 2017 Page 34 Technical Information Medium Version Controller ...
Страница 36: ...Issue 01 05 2017 Page 36 Certification ...
Страница 37: ...Issue 01 05 2017 Page 37 Certification ...
Страница 38: ...Issue 01 05 2017 Page 38 Certification ...
Страница 39: ...Issue 01 05 2017 Page 39 THIS PAGE IS LEFT BLANK INTENTIONALLY ...