Issue: 01.08.2020
Page 37
Technical Information
Dual Pressure Switch
Safety pressure switch settings:
The pressure switch fitted to condensing units with auto reset for low pressure is factory preset to 1.0 bar cut-out.
Do not set
pressure control below this setting.
Setting procedure for Low Pressure switch
Range: Turning the range adjusting screw (2) clockwise will decrease the cut-in pressure setting. Turning the range
adjusting screw anti-clockwise will increase the cut-in pressure setting.
Differential: Turning the differential adjusting screw (3) clockwise will increase the differential pressure setting.
Turning the differential adjusting screw anti-clockwise will decrease the differential pressure setting.
Lock the spindle with locking plate after setting.