Issue: 01.08.2020
Commissioning
Changing Set Point & Refrigerant Selection
1.
With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint”
button. Press ENTER button. Screen B01 is displayed.
1.
Using ENTER button, move the cursor from the ‘home’ position to the Compressor Setpoint and adjust value as required
by using UP or DOWN buttons.
2.
Press the ENTER button again to move the cursor to the Fan Setpoint and adjust the value as required. Please note that
the setpoint value of 16.0 bar is recommended for R407A/R407F/R448A/R449A operation.
3.
Press ENTER button once more to return the cursor to
4.
From screen B01, use the DOWN button to move to the next screen
5.
At screen B02, the Refrigerant Type can be selected. The defau
6.
To change the refrigerant, press ENTER to move the
7.
Use UP or DOWN buttons to scroll to different refrigerants.
8.
With required refrigerant selected, press ENTER button to return cursor to ‘home’ position.
9.
Press ESC button repeatedly to return to Home s
10.
The unit is now ready to run once the controller is set to ON.
IMPORTANT NOTE: The only refrigerants which should be selected are R407A, R407F, R448A & R449A.
Changing Set Point & Refrigerant Selection
With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint”
button. Press ENTER button. Screen B01 is displayed.
Using ENTER button, move the cursor from the ‘home’ position to the Compressor Setpoint and adjust value as required
Press the ENTER button again to move the cursor to the Fan Setpoint and adjust the value as required. Please note that
the setpoint value of 16.0 bar is recommended for R407A/R407F/R448A/R449A operation.
Press ENTER button once more to return the cursor to the ‘home’ position.
From screen B01, use the DOWN button to move to the next screen – B02.
At screen B02, the Refrigerant Type can be selected. The default refrigerant is set as R448A.
To change the refrigerant, press ENTER to move the cursor from the ‘home’ position to the refrigerant type.
Use UP or DOWN buttons to scroll to different refrigerants.
With required refrigerant selected, press ENTER button to return cursor to ‘home’ position.
Press ESC button repeatedly to return to Home screen.
The unit is now ready to run once the controller is set to ON.
The only refrigerants which should be selected are R407A, R407F, R448A & R449A.
Page 21
With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint” using DOWN
Using ENTER button, move the cursor from the ‘home’ position to the Compressor Setpoint and adjust value as required
Press the ENTER button again to move the cursor to the Fan Setpoint and adjust the value as required. Please note that
the setpoint value of 16.0 bar is recommended for R407A/R407F/R448A/R449A operation.
A.
cursor from the ‘home’ position to the refrigerant type.
With required refrigerant selected, press ENTER button to return cursor to ‘home’ position.
The only refrigerants which should be selected are R407A, R407F, R448A & R449A.
Содержание JEHSD-0400-B3-M-3
Страница 31: ...Issue 01 08 2020 Page 31 Dimensional Drawings JEHSD 0400 B3 M 3 JEHSD 0600 B3 M 3 JEHSD 0800 B4 M 3 ...
Страница 32: ...Issue 01 08 2020 Page 32 Electrical Wiring Diagram JEHSD 0400 B3 M 3 JEHSD 0600 B3 M 3 ...
Страница 33: ...Issue 01 08 2020 Page 33 Electrical Wiring Diagram JEHSD 0800 B4 M 3 ...
Страница 39: ...Issue 01 08 2020 Page 39 Technical Information Small Version Controller ...
Страница 41: ...Issue 01 08 2020 Page 41 Certification ...
Страница 42: ...Issue 01 08 2020 Page 42 Certification ...
Страница 43: ...Issue 01 08 2020 Page 43 Certification ...