![J&E Hall HallScrew HSO 2000 Series Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/jande-hall/hallscrew-hso-2000-series/hallscrew-hso-2000-series_installation-operation-and-maintenance-manual_3073464067.webp)
HSO 2024 to HSO 2035 Installation, Operation and Maintenance Manual
Issue 1.2 : 03/10
Publication 2-119
Page 67 of 94
HSO 2000 Series: Physical Data
Compressor Type
Single screw, open drive.
Compressor Rotation
Anticlockwise looking on the motor (driven) end. Under no circumstances should the
compressor run in the reverse direction.
For gas engine drive applications, an intermediate gearbox is required to reverse the
rotation of the prime mover.
Method of Drive
Direct coupled to foot mounted drive motor.
Physical Dimensions
Refer to Physical Dimensions and Connections
Capacity and Power
Refer to selection data.
Capacity Control
Compressor capacity infinitely variable from 100 % to approximately 10 % of full load
(depends on the operating conditions).
Slide valve position indication by 4 to 20 mA Linear Variable Displacement Transducer
(LVDT). DIN plug terminal box rating IP65.
Speed Ranges, Swept
Volumes and Weights
C
OMPRESSOR
N
ORMAL
S
PEED
R
ANGE
S
WEPT
V
OLUME
(m
3
/hr)
M
AX
A
LLOWABLE
S
HAFT
P
OWER
(kW)
W
EIGHT
(kg)
50
H
Z
60
H
Z
50
H
Z
60
H
Z
HSO 2024
1450 to
3600
rpm
853
1024
250
300
449
HSO 2028
1273
1528
350
420
564
HSO 2031
1728
2074
460
550
810
HSO 2035
1000 to
3600
rpm
2486
2983
650
780
1194
1
Sound Pressure Levels
@ 50 Hz (2 pole speed)
C
OMPRESSOR
T
OTAL
dB
‘A’
NR
C
ENTRE
F
REQUENCY
- Hz
125
250
500
1
k
2
k
4
k
HSO 2024
84
82
71.5
82
80
82
73
69
HSO 2028
86
84
73
84
82
84
75
71
HSO 2031
88
86
75
86
84
86
77
73
HSO 2035
90
88
77
88
85
88
79
75
1
Sound pressure level data applies to the compressor only. The sound pressure level for a standard air-cooled compressor
drive motor is usually higher.
The data refers to free-field conditions at a distance of 1 metre from the compressor periphery. It is important to remember
that on a specific installation the actual sound pressure level is considerably affected by the size and type of room, material
of construction and plant design. Adjoining pipework, including suction, can have a very substantial effect on the noise level.
Sound pressure levels given in dB refer to 2 x 10
-5
N/m
2
RMS.