background image

HSO 2024 to HSO 2035 Installation, Operation and Maintenance Manual 

Issue 1.2 : 03/10 

Publication 2-119 

Page 53 of 94 

During the running-in period, as oil is distributed throughout the system, it 
may be necessary to add extra oil from time to time until the overall oil 
content has stabilised.  Afterwards, it should only be necessary to replace 
the small quantity of oil lost during maintenance exercises, for example, 
changing the oil filter element. 

Applicable to plants charged with ammonia (R717), 

not

 applicable to 

other refrigerants. 

Unless the system is fitted with an oil still which automatically returns oil 
to the separator/reservoir, it is usually necessary to manually drain oil 
from vessels in the LP side of the system (suction separator, flooded 
evaporator or plate heat exchanger).  If there is very little oil to drain, this 
period can be extended. 

11.7. 

Checking for Leaks 

Check the plant daily during the first week or two of operation for leakage 
of refrigerant or oil; thereafter check for leaks weekly. 

11.8. 

Compressor Drive Motor Coupling 

After the first 12 hours of compressor operation, stop the plant and 
remove the guard from the drive coupling.  Remove the coupling 
membrane/spacer assembly. 

Check the tightness of the 

Taper Lock bush grubscrews securing the 

compressor half-coupling, check the half-couplings have not slackened-
off their shafts. 

Check and record the distance between shaft ends (DBSE) and the drive 
alignment.  The half-couplings should be aligned within 0.125 mm when 
using dial test indicators on each face and around the circumference.  
Refit the membrane/spacer assembly and the coupling guard. 

Recheck and record the DBSE and drive alignment after approximately 
the first 200 operating hours. 

11.9. 

Compressor and Drive Motor Holding-Down Bolts 

After approximately the first 200 compressor operating hours, check the 
tightness of the nuts securing the compressor and motor holding-down 
bolts. 

 

Содержание HallScrew HSO 2000 Series

Страница 1: ...HallScrew HSO 2000 Series Open Drive Single Screw Compressors HSO 2024 HSO 2028 HSO 2031 and HSO 2035 Manufactured after 06 03 Installation Operation and Maintenance Manual...

Страница 2: ...erved No part of this publication may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying recording or by any information storage or retrieval syst...

Страница 3: ...operation and the hazards involved All personnel should make a thorough study of these instructions before undertaking installation commissioning maintenance or repair procedures WARNING A minimum of...

Страница 4: ...t is at a voltage high enough to endanger life Before undertaking maintenance or repair procedures on electrical equipment personnel must isolate equipment from the electrical supply and test to verif...

Страница 5: ...t of refrigerant to atmosphere It is essential to restrict the amount which escapes to a minimum by pumping over and isolating the charge in another part of the system Where lubricating oil may be pre...

Страница 6: ...ilter element for example caution must be exercised as the oil will contain a certain amount of refrigerant which will be released when subjected to atmospheric conditions Refrigerant and lubricating...

Страница 7: ...4 1 Suction 16 3 4 2 Compression 17 3 4 3 Discharge 17 4 Capacity Control and Volume Ratio 18 4 1 Slide Valve Actuation 19 4 1 1 Minimum Load Interlock 19 4 2 Capacity Control Solenoid Valve Arrangeme...

Страница 8: ...5 Lubricating Oils 41 8 Prolonged Storage 42 8 1 Placing the Compressor into Store 42 8 2 Taking the Compressor out of Storage 43 9 Installing the Compressor 44 9 1 Lifting the Compressor 44 9 2 Makin...

Страница 9: ...ide Valve in Operation 18 Fig 3 Capacity Control Arrangement Using Separate Pairs of Solenoid Valves 22 Fig 4 Capacity Control Arrangement Using a 4 Way Solenoid Valve 24 Fig 5 HBLVDT Arrangement and...

Страница 10: ...tial Information WARNING This denotes an immediate hazard with a high likelihood of personal injury or death if instructions including recommended precautions are not followed There is also a potentia...

Страница 11: ...250 or better d If the system is fitted with an economiser fit an adequately sized strainer in the economiser suction line The strainer must have a mesh aperture of 250 or better e To prevent excessiv...

Страница 12: ...place Under no circumstances must the HallScrew compressor be used to evacuate or pump out the system The evacuation procedure is described in publication Part E Evacuation and Dehydration available...

Страница 13: ...ork i e that part of the machine which performs the compression function consists of three rotating parts there are no eccentric or reciprocating motions These fundamental components comprise the cyli...

Страница 14: ...ain rotor can be likened to the cylinders of a reciprocating compressor the star rotor teeth taking the place of conventional pistons Instead of using suction and discharge valves gas flow in and out...

Страница 15: ...ough solenoid valves which respond to signals from the plant control system The solenoid valves direct oil to each end of the compressor capacity control cylinder via two connections positioned at the...

Страница 16: ...As the main rotor turns the effective length of the flutes increases with a corresponding increase in the volume open to the suction chamber Diagram 1 Fig 1 clearly shows this process As flute a assum...

Страница 17: ...scharge port Compression immediately ceases as the gas is delivered into the discharge manifold The star rotor tooth continues to scavenge the flute until the flute volume is reduced to zero This comp...

Страница 18: ...s known as the built in volume ratio VR and is an important characteristic of all fixed port compressors In order to achieve maximum efficiency the pressure within the flute volume at the end of the c...

Страница 19: ...n balanced gas loads and low bearing loads within the compressor The position of the slot at the suction end of the slide and the position of the moving delivery port can both be chosen to give the de...

Страница 20: ...at start up only A 4 way valve or separate pairs of solenoid valves can be used Continuously running or demand oil pump All oil pump applications compressor located in a Zone 1 or Zone 2 hazardous are...

Страница 21: ...nnected to the unload side of the piston which controls the speed of loading while the valve connected to the load side of the piston controls the speed of unloading this is illustrated in Fig 3 Closi...

Страница 22: ...De energise open De energise close Hold slide valve position De energise close Energise close De energise close 1 Flow control valves enclosed in boxes incorporate NRV as shown in Fig 11 Fig 3 Capacit...

Страница 23: ...e spool to the centre off position closing all the ports and hydraulically locking the capacity control piston and slide valves at the desired load position 4 4 4 Flow Control Valves The capacity cont...

Страница 24: ...energise De energise No flow 1 Flow control valves enclosed in boxes incorporate NRV as shown in Fig 11 2 The solenoids on the 4 way valve are normally closed energise to open Fig 4 Capacity Control A...

Страница 25: ...ortance that it is both sized and set up correctly 4 5 1 Inverter Size The inverter must be sized to deliver the maximum current taken by the compressor motor at the maximum power conditions in most c...

Страница 26: ...Transducer HBLVDT External wiring connections are illustrated in Fig 5 and Fig 6 Two LEDs are provided red for calibration and green for slide valve position indication An explosion proof version of t...

Страница 27: ...ng enough for the procedure to be completed The HBLVDT should be wired as shown in Fig 5 or Fig 6 check this point a Start the compressor if it was not already running If the compressor will not start...

Страница 28: ...lustrated is recommended DIN Plug Connector Safe Area 24 V dc supply 1 Ex Area Zone 1 0 V dc common 2 or Zone 2 4 to 20 mA signal 3 No connection Fig 6 HBLVDT External Wiring Connections for Explosion...

Страница 29: ...interlocked to prevent starting unless the slide valves are at minimum load refer to 4 1 1 therefore either of the above conditions will result in the controller refusing to allow the compressor to st...

Страница 30: ...a signal conditioning module is available part number 2848 601 for applications where this is not possible The module is suitable for DIN rail mounting refer to Fig 8 The method of 4 to 20 mA signal...

Страница 31: ...Number HallScrew Compressor Series MSI LVDT HBLVDT 7876 143 7876 120 HS 2024 HS 2000 7876 144 7876 121 HS 2028 7876 145 7876 122 HS 2031 7876 146 7876 123 HS 2035 1 The J E Hall part number appears o...

Страница 32: ...face element located in the cover plate attached to the shaft seal housing Each sealing face has a highly polished optically flat surface separated by a thin oil film which provides an effective seal...

Страница 33: ...ion process when the pressure of the gas trapped in the flutes is considerably lower than discharge pressure this means that in the majority of instances the system pressure difference can be used to...

Страница 34: ...the internal drain ceases to function In such applications and for all low stage booster and other low pressure difference applications where a continuously running oil pump is used provision must be...

Страница 35: ...the separator into the compressor Additionally as the separator efficiency changes with load and operating conditions then the amount of oil carried into the system through the separator will also va...

Страница 36: ...maintain an oil temperature 20 C above the ambient temperature thereby preventing refrigerant migration into the oil and the resultant loss of viscosity and potential foaming The oil heaters must be...

Страница 37: ...al examples are under low ambient conditions low load operation and most low stage booster applications If the difference between absolute discharge pressure measured at the outlet from the oil separa...

Страница 38: ...start up only Not used ODP2 by transducers Oil injection pressure Discharge pressure during start up only 1 Designated ODPS on applications with no oil pump or a continuously running oil pump only on...

Страница 39: ...e start up oil pump runs to establish a discharge oil pump pressure differential in excess of the ODP2 value After allowing sufficient time for the pressure differential to rise ODP2 is brought into t...

Страница 40: ...element should be capable of filtering to 10 microns or better 10 A typical filter specification would be 25 75 10 3 5 1 This specification indicates that the filter element will pass 1 particle in 75...

Страница 41: ...er to publication 2 122 Compressor Cooling 7 5 Lubricating Oils The choice of lubricant depends on the refrigerant the type of system and the operating conditions As choosing the correct lubricant is...

Страница 42: ...gland seal faces these surfaces should be lightly greased before the compressor is placed in store If the compressor drive half coupling is already fitted this must be removed from the mainshaft Purge...

Страница 43: ...tial start in order to minimise the possibility of damage NOTE specially negotiated guarantee terms to cover stored compressors will not be honoured unless these procedures are followed a Carefully pu...

Страница 44: ...from rust dirt or burrs Lift the compressor and make the same check on the underside of the compressor s four mounting feet As the compressor is being positioned insert the holding down bolts through...

Страница 45: ...Rotate the mainshaft by hand to ensure that the motion work turns smoothly and evenly If the compressor proves very stiff to turn turns unevenly or rotation is accompanied by any unusual noise contac...

Страница 46: ...k incoming main supply cables and fuses are correctly sized refer to the wiring diagrams supplied d Check that the compressor package unit is correctly earthed Depending on circumstances this may requ...

Страница 47: ...rst time If there is any doubt whether the motor has been affected by moisture the value of the motor insulation resistance must be checked The motor should not be run if the insulation resistance exc...

Страница 48: ...re of approximately 45 C is about right If the heaters are thermostatically controlled the thermostat should be set to maintain the desired oil temperature NOTE the oil heaters must NOT be energised w...

Страница 49: ...differential to become established ODPS is brought into circuit Oil is now being supplied to the compressor under the action of the system pressure differential monitored by ODPS If the system pressur...

Страница 50: ...the cooling water outlet to give an oil temperature of 40 C If automatic flow regulation is not fitted a manual valve must be throttled to achieve the correct temperature If the compressor is fitted w...

Страница 51: ...ed lines Make sure that stop valves are opened as required before restarting NOTE in the case of prolonged shutdown periods the procedures described under 13 5 9 Prolonged Shutdown should be followed...

Страница 52: ...100 compressor operating hours After the commissioning period clean the suction strainer annually or at intervals of 5 000 operating hours whichever is the sooner 11 3 Oil Filter Renew the oil filter...

Страница 53: ...hecking for Leaks Check the plant daily during the first week or two of operation for leakage of refrigerant or oil thereafter check for leaks weekly 11 8 Compressor Drive Motor Coupling After the fir...

Страница 54: ...enerally applicable where suction and discharge stop valves are provided Close the discharge gauge valve and disconnect the gauge line Connect a suitably sized refrigerant recovery unit to the gauge v...

Страница 55: ...d disconnect the refrigerant recovery unit and allow air to enter the compressor via the gauge valve 12 5 Opening up the Compressor Before opening up drain off any oil left behind in the compressor WA...

Страница 56: ...te and dehydrate the compressor and all other parts of the system open to atmosphere Adopt the procedures described in publication Part E Evacuation and Dehydration available from J E Hall Internation...

Страница 57: ...y refrigerant if used Pressure test certification The component is capable of withstanding the pressures likely to be encountered within the system For plants located within the European Economic Area...

Страница 58: ...arises the HallScrew compressor should not need opening up until the first inspection after six years or 25 000 operating hours run have elapsed whichever is the sooner Maintenance during the guarant...

Страница 59: ...all other refrigerants Check the sight glass moisture indicator If there is evidence of an increase in the moisture content of the system corrective action must be taken immediately by changing the re...

Страница 60: ...may be necessary to fit a new element before this interval hours run time expires if the oil filter pressure drop exceeds the clean filter pressure drop plus 1 4 bar d Clean strainers throughout the s...

Страница 61: ...loves goggles and a respirator must be worn refer to Safety Equipment in the publication for the refrigerant in Section 5 If new coalescing elements are to be fitted after removing the old elements th...

Страница 62: ...valves are opened as required before restarting WARNING The compressor must NEVER be started with the discharge stop valve closed or partially closed b It is important to run the plant for at least on...

Страница 63: ...er cores not usually applicable to plants charged with ammonia R717 applicable to all other refrigerants Check pressure and temperature safety controls operate correctly Check the condition of the cou...

Страница 64: ...ssue 1 2 03 10 13 7 Oil Acid Content Record Plants charged with refrigerant other than ammonia R717 Each time the oil s acid content is checked record the value in Table 7 ACID CONTENT SIGNATURE PRINT...

Страница 65: ...Page 65 of 94 Appendix 1 Compressor Data HSO 2000 Series Compressor Model Nomenclature HSO 2000 Series Physical Data HSO 2000 Series Starting Torque Characteristics HSO 2000 Series Limits of Operatio...

Страница 66: ...Nominal 0 Without motor Motor Voltage 0 No voltage without motor Refrigerant A R134a F R404a B R22 G R717 C R407c H R23 D R410a X Other E R507a Voltage Auxiliary 0 No voltage Capacity Indicator 0 No c...

Страница 67: ...COMPRESSOR NORMAL SPEED RANGE SWEPT VOLUME m3 hr MAX ALLOWABLE SHAFT POWER kW WEIGHT kg 50 HZ 60 HZ 50 HZ 60 HZ HSO 2024 1450 to 3600 rpm 853 1024 250 300 449 HSO 2028 1273 1528 350 420 564 HSO 2031...

Страница 68: ...FULL LOAD TORQUE Does not include accelerating torque SYSTEM PRESSURE RATIO 2000 Series Starting Torque Characteristics 20 30 40 50 60 70 0 20 40 60 80 100 Speed Full Load Torque Does not include acce...

Страница 69: ...Compressors With Liquid Injection Oil Cooling Standard 7 Controlled discharge temperature Discharge high temperature cut out Injected oil high temperature cut out 8 75 C 100 C maximum 80 C 1 Assemble...

Страница 70: ...sducers and controller software programme Refer to Table 4 1 Oil temperature High Cut out or thermistor 80 C Temperature in oil line to compressor Oil flow Low Oil flow switch Contacts close at 0 15 l...

Страница 71: ...0 PCD 125 mm 5 NB BS 4504 Table 40 3 8 x M24 on 220 PCD 150 mm 6 NB BS 4504 Table 40 3 8 x M24 on 250 PCD Suction pressure gauge 1 3 8 BSP x 6 mm OD male stud coupling Discharge pressure gauge 1 3 8 B...

Страница 72: ...Gauge Discharge End Cover Oil Drain Gland Oil Feed Economiser Connection Top Capacity Control Load Capacity Control Unload Discharge Pressure Gauge Economiser Connection Bottom Discharge Top Option D...

Страница 73: ...normally closed Dual relief valve to atmosphere Thermostatic expansion valve Sight glass on vessel Liquid drainer Sight glass in line Heater Strainer Opto sensor in drain line Oil filter Oil pump 4 Wa...

Страница 74: ...ion Oil Filter Oil Cooler Water Air or Refrigerant Cooled Instead of Liquid Injection refer to 7 4 Compressor Cooling Circuit Completion When Using Liquid Injection Cooling PSH Discharge PI PI Oil ODP...

Страница 75: ...r if Double Duplex Oil Filters Required Oil Separator Reservoir Coalescing Elements for Oil Separation Down to 5 ppm Weir LSL Oil Cooler Water Air or Refrigerant Cooled Instead of Liquid Injection ref...

Страница 76: ...Separation Down to 5 ppm Weir LSL PI OD P2 HP LP Oil Oil Filter PI Oil Drain Line FS Oil Pressure After Filter TE HT Oil Second Filter if Double Duplex Oil Filters Required Oil Cooler Water Air or Ref...

Страница 77: ...Gauge C 30 20 10 0 10 20 30 40 50 60 70 60 50 40 30 20 10 0 10 20 Suction Gauge C Continuously running oil pump required below this line Booster This diagram is approximate for guidance only Refer to...

Страница 78: ...0 0 10 20 30 40 50 60 70 60 50 40 30 20 10 0 10 20 Suction Gauge C Continuously running oil pump required below this line Booster This diagram is approximate for guidance only Refer to HallScrew selec...

Страница 79: ...0 30 40 50 60 70 80 90 50 40 30 20 10 0 10 20 30 Suction Gauge C Continuously running oil pump required below this line Booster This diagram is approximate for guidance only Refer to HallScrew selecti...

Страница 80: ...10 0 10 20 30 40 50 60 70 60 50 40 30 20 10 0 10 20 Suction Gauge C Continuously running oil pump required below this line Booster This diagram is approximate for guidance only Refer to HallScrew sel...

Страница 81: ...10 20 30 40 50 60 70 60 50 40 30 20 10 0 10 20 Suction Gauge C Continuously running oil pump required below this line Booster This diagram is approximate for guidance only Refer to HallScrew selectio...

Страница 82: ...e Kit serial number ends 500 N02210038 95822 445 1 1 Capacity Control Slides 8 N A Capacity Control Slide Kit 2 2 VR serial number ends 500 N02860038 95822 403 1 8 N A Capacity Control Slide Kit 2 6 V...

Страница 83: ...N02210039 95822 545 1 1 Capacity Control Slides 8 N A Capacity Control Slide Kit 2 2 VR serial number ends 500 N02860042 95822 503 1 8 N A Capacity Control Slide Kit 2 6 VR serial number ends 500 N02...

Страница 84: ...city Control Slide Kit 2 2 VR serial number ends 500 N02860046 95822 603 1 8 N A Capacity Control Slide Kit 2 6 VR serial number ends 500 N02860047 95822 604 1 8 N A Capacity Control Slide Kit 3 5 VR...

Страница 85: ...l number ends 500 N02860051 95822 704 1 8 N A Capacity Control Slide Kit 3 5 VR serial number ends 500 N02860052 95822 705 1 8 N A Capacity Control Slide Kit 4 9 VR serial number ends 500 N02860053 95...

Страница 86: ...designing a log sheet for the plant either on paper or as an electronic form held in a computer database there are certain pressures temperatures and flow rates which are common to nearly every plant...

Страница 87: ...OIL COOLER COOLING MEDIUM Inlet Temperature C Outlet Temperature C Rate of Flow m3 h CONDENSER COOLING MEDIUM Inlet Temperature C Outlet Temperature C Rate of Flow m3 h 3 Ambient Dry Bulb Temperature...

Страница 88: ...application because it has a pre programmed function which does not allow the required Factor to be set up also mA cannot be used as a unit because this is the same as the input units It is therefore...

Страница 89: ...nput Output OK Relay Analogue Out OK Characteristic OK 0 to 20 mA Flashing 4 to 20 mA NE4 Flashing 6 235 mA OK 4 to 20 mA NE4 Set saved 9 0 mA Temporary value ESC Characteristic Start Value OK Numeric...

Страница 90: ...teristic Start Value End Value OK Numeric Teach In OK 15 76 mA Flashing 15 1 mA OK 15 76 mA End value saved 20 mA Maximum load set ESC Teach In ESC End Value ESC Analogue Out ESC Output Maximum load E...

Страница 91: ...g 10 49 Set value 100 15 765 6 235 OK 10 49 Multiplying factor set ESC Factor ESC Input Min load ESC 0 000 slide valve setting 4 mA Max load 100 0 slide valve setting 20 mA 1 Operation can be done wit...

Страница 92: ...Trip value set ESC Trip Hysteresis OK 20 98 For example Flashing 2 000 Set value for example Flashing OK 2 000 Hysteresis value set ESC Hysteresis ESC Relay ESC Output Min load ESC 0 000 4 mA 1 Operat...

Страница 93: ...HSO 2024 to HSO 2035 Installation Operation and Maintenance Manual Issue 1 2 03 10 Publication 2 119 Page 93 of 94 This page intentionally blank...

Страница 94: ...in any form or by any means electronic or mechanical including photocopying recording or by any information storage or retrieval system without permission in writing from the copyright holder The cop...

Отзывы: