background image

Installation manual: OASiS security system JA-82KRC-US   

13 / 21 

MKH51400

 

  If  the  unconfirmed entrance  delay  is  confirmed  by  an  instant 

detector  it  will  trigger  an  internal  warning  alarm  immediately 
(e.g.  an  internal  siren)  and  if  the  entrance  delay  times  out 
then an external alarm will be triggered. 

  An unconfirmed alarm can be confirmed by any other intruder 

detectors in the system as long as the detectors are assigned 
to a set (armed) section. 

  The  confirmation  of  intruder  alarms  has  no  effect  on  fire, 

panic, 24-hour, tamper, or technical alarms. These alarms are 
triggered immediately without confirmation. 

 

Note:

  When  the  first  detector  is  triggered  it  begins  a  process 

which  waits  40  minutes  for  any  possible  confirmation  of  the 
alarm (unconfirmed alarm status) during which the system works 
exactly  the  same  way  as  if  the  confirmation  function  had  not 
been enabled. 

    

 

Warning: 

  If  intruder  alarm  confirmation  is  enabled,  it  is 

necessary to install enough detectors in the building to detect an 
intruder even if he/she is only moving in one particular place. 

 

Factory default setting:

 confirmation disabled 

 

12.16.  Exit delay beeps 

The exit delay can be indicated by beeps from the keypad and 

internal siren. The beeps get faster in the last 5 seconds. 

 

3 3 1

 

Beeps 

enabled

 

3 3 0

 

Beeps 

disabled

 

 

Factory default setting:

 Beeps enabled. 

 

12.17.  Exit  delay  beeps  while  partially  setting 

(arming) 

The exit delay caused by partial setting, e.g. using the A or B 

key,  can  also  be  indicated  by  keypad  beeps  and  internal-siren 
beeps. The beeps get faster in the last 5 seconds. The feature is 
linked to 33x setting. 

 

3 4 1

 

Beeps 

enabled

 

3 4 0

 

Beeps 

disabled

 

 

Factory default setting:

 Beeps disabled. 

 

12.18.  Entrance delay beeps 

The  entrance  delay  can  be  indicated  by  keypad  beeps  and 

internal-siren beeps: 

 

3 5 1

 

Beeps 

enabled

 

3 5 0

 

Beeps 

disabled

 

 

Factory default setting:

 Beeps enabled. 

 

12.19.  Setting (arming) confirmation by wired-siren 

chirp 

A hard-wired siren connected to the IW terminal of the control 

panel can audibly indicate setting by one beep, unsetting by two 
beeps and unsetting after an alarm by three beeps. Four beeps 
mean an invalid attempt at setting the system has occurred.  

 

3 6 1

 

Chirps 

enabled

 

3 6 0

 

Chirps 

disabled

 

 

Note:

 In JA-80L wireless sirens, this function can be individually 

enabled for each siren. (see the siren manual). 

Factory default setting:

 Hard-wired siren chirps disabled 

 

12.20.  Sirens always sound during audible alarms 

Using  this  sequence  it  is  possible  to  disable  internal  and 

external  sirens  (IW  and  EW)  if  any  part  of  the  system  is  unset 
(partial setting), i.e. when someone is home. 

3 7 1

 

Sirens always sound during audible alarms 

3 7 0

 

Sirens  only  sound  during  audible  alarms  when 
all sections are set, i.e. no one is home 

 

Factory  default  setting: 

Sirens  always  sound  during  audible 

alarms. 

 

12.21.  Wireless siren alarm enabled (IW and EW) 

This setting is for enabling and disabling wireless sirens in the 

system:   

3 8 1

 

wireless sirens enabled 

3 8 0

 

wireless sirens disabled 

 

Note:

 This setting has no effect on wired output terminals. 

Factory default setting:

 wireless sirens enabled 

 

12.22.  Auto-bypass user approval via the 

 key 

 

The  system  has  a  built-in  auto-bypass  function  so  that  if  any 

number of detectors are being triggered during setting (arming) 
then they will be bypassed and ignored automatically. 
If  auto-bypass  approval  by  the  user  is  disabled,  then  during 
setting (arming) the system notes which detectors are currently 
triggered  and  automatically  bypasses  them  without  consulting 
the user.  

If however, auto-bypass user approval is enabled, then during 

setting (arming), the system notes which detectors are currently 
triggered  and  displays  informative  text  on  the  keypad  and  only 
bypasses them if the user approves the bypassing by keying in a 

 within 6 seconds of being notified. 

 

3 9 1 

Approval is requested from the user 

3 9 0

 

Bypassing  occurs  automatically  without  user 
approval 

 

Notes regarding setting the system with (a) triggered detector(s): 

 

Details  on  currently  triggered  detectors  can  be  viewed  by 
pressing the 

?

 key (e.g. open doors or windows). 

 

If  a  wireless  keyfob  is  used  to  set  the  system  and  auto-
bypass  user  approval  is  enabled, the system  will set  without 
bypass  approval,  i.e.  setting  by  keyfob  does  not  trigger  an 
approval request.  

 

The automatic bypass of a detector will end  after the detector 
has been de-triggered (for example if a door is closed) 

 

If auto-bypass user approval is enabled and Service mode is 
being  exited  while  a  detector  is  being  triggered,  the  installer 
will  be  notified  about  the  bypass.  The  installer  can  then 
approve the bypass by pressing #  twice. 

 

To comply with the EN-50131-1standard 391 should be set.

 

 

Factory  default  setting:

  Bypassing  occurs  automatically 

without user approval. 

 

12.23.  Final-door detectors   

In  this  mode,  up  to  5  detectors  can  be  defined  as  final-door 

detectors  and  assigned  to  addresses  01  to  05  or  46  to  50  in 
order  to  make  leaving  a  building  much  easier,  especially  via  a 
garage:  

65x 

where 

x = 0 

none,  

x = 1

 

detectors on addresses 01 to 05, 

x = 2

 

detectors on addresses 46 to 50.

 

 

Description of final-door detector mode: 

  If a final-door detector is used in the system then the value of 

x for exit delay programming is multiplied by 30 s (see 12.1) 
thereby  extending  the  delay,  and  if  an  entrance  delay  is 
triggered  by  a  final-door  detector  then  the  value  of  x  for  the 
entrance delay is also multiplied by a larger value of 30 s. 

  A final-door detector should be programmed to have a natural 

reaction.  

  Door/window  detectors,  hard-wired  control  panel  inputs  or 

hard-wired inputs in the wireless keypad unit can be used as 
final-door detectors. 

  If  a  final-door  detector  is  used  for  a  garage  door,  no  instant 

detectors  should  be  inside  the  garage.  Next-delay  detectors 
would however be acceptable. 

 

Setting (arming) the system with a final-door detector: 

Содержание JA-82KRC-US

Страница 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Страница 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Страница 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Страница 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Страница 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Страница 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Страница 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Страница 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Страница 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Страница 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Страница 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Страница 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Страница 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Страница 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Страница 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Страница 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Страница 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Страница 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Страница 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Страница 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Страница 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Отзывы: