background image

Installation manual: OASiS security system JA-82KRC-US   

10 / 21 

MKH51400

 

Engineer reset 

668x 

6851 = YES     6850 = N0

 

NO

 

 

Annual check requirement display 

If  enabled  then  12  months  after  exiting  Service  Mode  an 
annual technical check request is displayed on the keypad unit 
(mobile phone & ARC notification optional)

 

690x 

6901 = YES     6900 = NO 

NO 

 

Only single alarm indication 

If  enabled  then  another  intruder  alarm  can  not  be  triggered 
during an intruder alarm currently in progress.

 

691x 

6911 = YES     6910 = NO 

NO 

 

Setting (arming) by service code 

692x 

6921 = YES     6920 = NO 

NO 

only with the master 
code holder’s  
approval  

Audible panic alarm 

693x 

6931 = YES     6930 = NO 

NO 

 

Higher control-panel receiver-sensitivity 

Extends the communication range if there is no RF 
interference 

 

694x 

6940 = normal    6941 = higher 

normal 

 

Access by Code plus

 

Card

  

If enabled and there is a code and card assigned to the same 
user, then both of them must be presented for setting (arming) 
control (in any order).

 

695x 

6951 = Code+Card     

 6950 = Code or Card 

code or 

card 

 

Audible 24h intruder alarm

 

696x 

6961 = YES     6960 = NO 

YES 

 

Service mode only with S Master code 

697x 

6971 = YES     6970 = NO 

NO 

 

Device  reactions and  section  assignment 

(detectors, 

key fobs, control panel and keypad inputs) 

 

A  detector’s  natural  reaction

  can  be  INS,  DEL  or  Fire 

(selectable in the detector) 

 

The  natural  reaction

  of 

Control  panel  &  Keypad  wired 

inputs  

is DEL 

Keyfob  natural  reactions: 

  (or

)=  SET  (arm)  , 

 

(or

)= UNSET (disarm) and both simultaneously = Panic. If a 

reaction  from  2  to  8  is  selected  (see  opposite),  only  the  key 

 (or

) and double buttons 

 + 

 (

+  ) will have it. 

The 

  (

)  button  has  no  effect  (can  still  be  used  for 

controlling UC/AC receivers).

 

 

Assignment to sections

 will only have an effect on partial 

arming or if the system is split (except PG output control)   

 

For  partial  arming, 

a

 

pair  of 

keyfob

  buttons  assigned  to 

section: 

A has the effect:

 

 (or

)=SET A, 

 (or

)=SET AB  

B has the effect:

 

 (or

)=SET A, 

 (or

)=SET AB 

C has the effect:

 

 (or

)=SET ABC, 

 (or

)=UNSET 

ABC

 

 

In a split system, a keyfob

 button pair assigned to section: 

A=SET/UNSET A, B =SET/UNSET B, C =SET/UNSET ABC  

 

61 nn r s 

Code (card) reactions and section assignment 

  A  code  (card)  may  have  the  same  kind  of  reaction  as 

devices 

62 nn r s 

 
nn 

address

 01 to 50  

r = reaction

 

 0 disabled (incl. tamper sensor) 
 1 

Natural 

– this means: 

for detectors

=selected by 

DIP switch in the detector,  

for wired inputs

=DELay, 

for Codes 
(cards

)=SET/UNSET 

 2 Panic 
 3 Fire 
 4 24 hours 
 5 Next DELay 
 6 INStant 
 7 SET (arm) 
 8 PG control (s: 1=PGX,         
2=PGY,3=PGX+PGY) 
 9 SET/UNSET (toggle) 

 

 

 

s = section

 1=A, 2=B, 3=C - has 

to be entered even if the system 
is not split and setting 
(arming)has no meaning.  
In a split system, a code (card) 
assigned to C will SET/UNSET 
all ABC sections 

 

 
 
 
 
 
 
 
 

all Natural 

in C 

 
 
 

 
 
 

Enrollment by keying in production codes 

 60 nn xxxxxxxx 

nn

 = address 01 to 50, 

xxxxxxxx

 = last 8 digits of the 

production code (below the bar code on the device)  

Automatic 

Daily 

Setting/Unsetting 

schedule 

(arming/disarming) 

64

nahhmm

 

n –

 action sequence index (0 to 

9)  

a –

 action: 

 

0=no action 

 1=SET ABC 
 2=UNSET ABC 
 3=SET A 
 4=SET B (if unsplit then AB) 
 5=UNSET A (if unsplit then ABC) 
 6=UNSET B (if unsplit then ABC) 

hh -

 hours, 

mm - 

minutes 

 

No action 

 

The scheduled 
actions will happen 
every day 

Changing the service code 

5 NC NC 

NC = new code

 (4 digits)  

8080 

enter NC twice  

Go to maintenance mode 

292 

switches to 

maintenance

 

mode 

 

Setting the internal clock 

4 hh mm DD MM YY

 

00:00 1.1.00   

Editing keypad text 

Text for device names, code names and PG output names 
are stored in each individual keypad.  
 

Press and hold the 

?

 key to enter text editing 

(the first character of the first address name 
will start flashing). Then use keys: 

 and 

 to select some text (or an address)  

1

 & 

7

  character selection (A,B,C,D...8,9,0) 

4

 & 

5

 cursor (to the left & right) 

2

 to erase a character 

# = 

# = 

# = 

# = 

exit editing

 and save changes 

 
Device 

Only capital letters 
can be entered this 
way. If there are 
multiple keypads, 
each must be edited 
individually this way 
or all of them can be 
easily  programmed 
via OLink software 

 

Содержание JA-82KRC-US

Страница 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Страница 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Страница 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Страница 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Страница 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Страница 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Страница 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Страница 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Страница 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Страница 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Страница 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Страница 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Страница 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Страница 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Страница 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Страница 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Страница 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Страница 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Страница 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Страница 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Страница 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Отзывы: