background image

Installation manual: OASiS security system JA-82KRC-US   

11 / 21 

MKH51400

 

12.2.  Exit delay time 

 

An  exit  delay  time  occurs  while  setting  (arming)  the  system. 

During this time period delayed or next-delayed detectors can be 
triggered without an alarm occurring. To program the delay time, 
enter: 

20x 

where 

is a number from 1 to 9 determining the duration 
in steps of tens of seconds (1=10 s, 2=20 s,....) 

If there is a final-door detector in the system then the exit delay 
is multiplied by 30 s instead (1=30 s, 2=60 s,...). 

Example:

  To  program  a  20  seconds  exit  delay,  use  the 

sequence  202  (if  there  is  a  final  door  detector,  a  60  seconds 
delay will result).  

Factory default setting:

 x = 3 

 
 

12.3.  Entrance delay time   

The  entrance  delay  time  is  provided  to  unset  (disarm)  the 

system  after  a  first  delayed  detector  has  been  triggered.  To 
program this time, enter: 

21x 

where 

is a number from 1 to 9 determining the delay in 
multiples of 5 seconds (1=5 s, 2=10 s,....) 

If the entrance delay is triggered by a final-door detector, then 

parameter x is multiplied by 30 s instead. (1=30 s, 2=60 s,...) – 
in this case it means that the entrance delay would be six times 
longer than if it had been triggered by an ordinary detector.   

Example:

  To  program  a  20  seconds  entrance  delay,  enter  the 

sequence  214  (if  the  delay  has  been  activated  by  a  final-door 
detector, a 120 seconds delay will result instead). 

Factory default setting:

 x = 4  

 

12.4.  Alarm duration time 

This  parameter  limits  the  duration  of  a  triggered  alarm.  After 

the  alarm  state  expires,  the  control  panel  will  return  to  its 
previous  state,  i.e.  as  before  the  alarm  occurred.  The  alarm 
state can also be terminated by an authorised user. To program 
the alarm duration enter:  

22x 

where 

is

 

a  number  from  0  to  9  determining  the  alarm 

duration: 0 = 10 s, 1 = 1 min., 2 = 2 min. up to 8 
= 8 min., 9 = 15 min.   

Note:

  There  can  be  up  to  5  different  alarms  in  the  system: 

intruder, tamper, fire, panic, and technical alarm.   

 

Example:

 Alarm duration of  5 min. = sequence 225 

Factory default setting:

 

 

4 minutes 

 

12.5.  PGX and PGY functions 

 

The  functions  of  PGX  and  PGY  can  be  programmed  by 

entering sequences: 

2 3 x

   for PGX 

2 4 x

   for PGY 

 

where  

x

  determines the PG function or the event which triggers 

a change of PG state:  

Unsplit system 

Split system 

Completely (ABC) set 
= PG on 

Alarm A = PG on 

Anything set = PG on 

Alarm B = PG on 

AB set 

(not ABC) 

= PG 

on 

Entrance delay A = PG on 

Fire alarm = PG on 

Entrance delay B = PG on 

Panic = PG on 

A set = PGX on, B set = PGY on 

Any alarm = PG on 

(excluding Panic) 

Panic A = PGX on 
Panic B = PGY  on 

AC dropout = PG on 

Fire = PGX on, dropout =PGY on  

7*  ON/OFF   
8*  2 seconds pulse  

 

 

*  The  ON/OFF  and  2  second  pulse  functions  can  be 
controlled from the keypad by keying in * 8, *9 or using the 
arrow keys

 

 

(see 12.27) or they can be operated by a code 

or  card.  These  PG  output  functions  can  also  controlled  by 
signals from keyfobs or detectors (see 12.41). 

Notes:  

 

The  PGX  and  PGY  outputs  are  not  only  provided  as  control 
panel  terminals,  but  the  signals  are  also  wirelessly 
transmitted for UC and AC modules. 

 

The  status  of  PGX  and  PGY    outputs  can  be  displayed  by 
pressing the “

?”

 key. The names of the outputs can be edited  

– see 

12.47

Example (for unsplit systems): 

Assigning an ON/OFF function 

to the PGX output = sequence 237. Assigning a panic function to 
the PGY output = sequence 244. 

Factory default setting:

 PgX= ON/OFF, PgY= anything set 

 

12.6.  Changing 

telephone 

numbers 

in 

maintenance mode 

If  the control  panel  is  equipped  with  a  JA-80Y,  JA-80V  or JA-

80X communicator, then this sequence enables the 

holder of the 

master  code  (system  administrator) 

to  program  telephone 

numbers 

for 

alarm 

reporting 

in 

maintenance 

mode. 

Programming  telephone  numbers  is  the  same  as  in  Service 
mode (see communicator manual): 

2 5 1

 

programming 

enabled

 

2 5 0

 

programming 

disabled

 

 

Factory default setting:

 

programming disabled

 

12.7.  Radio interference indication 

The  control  panel  is  capable  of  detecting  and  indicating  radio 

communication  jamming.  If  this  function  is  enabled,  any  radio 
jamming longer than 30 s will trigger fault indication. 

2 6 1

 

enabled 

2 6 0

 

disabled  

 

Factory default setting:

 disabled. 

 

Note:  In  some  places  the  system  can  be  permanently  or  occasionally  
affected  by  radio  interference,  e.g.  by  nearby  radar  stations,  TV 
transmitters etc. In most cases the system can tolerate such effects, but 
with this anti-jamming function disabled.  

12.8.  Radio communications supervision 

If  enabled,  the  control  panel  can  routinely  check  wireless 

connections  to  its  devices.  If  communication  with  a  particular 
device  is  lost,  the  control  panel  can  communicate  a  fault 
indication to the user:   

2 7 1

 

indication 

enabled

 

2 7 0

 

indication 

disabled

  

Notes:  

 

In the Oasis system, communication is checked every 9 mins. 

 

In  detectors  used  for  car  protection,  (JA-85P,  JA-85B)  it  is 
possible to disable radio communication supervision. It allows 
car detectors to be excluded from supervision to avoid alarm 
triggering when driving the car away from the system. 

 

Random  dropouts  in  communication  can  occur  in  some 
installations  near  e.g.  airports  or  TV  towers.  The  system  is 
still  reliable  in  such  situations  as  high-priority  transmissions 

Содержание JA-82KRC-US

Страница 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Страница 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Страница 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Страница 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Страница 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Страница 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Страница 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Страница 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Страница 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Страница 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Страница 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Страница 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Страница 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Страница 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Страница 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Страница 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Страница 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Страница 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Страница 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Страница 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Страница 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Отзывы: