60
Factory
setting
Position
Setting of
Factory
setting
Position
Setting of
P2.3
DHW-temperature
45ºC
P2.4
DHW hysteresis
5ºC
P4.1
Clock setting HP
not active
P4.1.1
Setting level HP
0ºC
P4.2
Clock setting add. heat
not active
P4.3
Clock setting DHW
not active
P5.1
Select operation mode
A
P5.2
Conn. cap. electrical cass.
2/3
P5.4
Only add. heat
Off
P5.5
Add. heat yes/no
yes
P5.7
External controls
0
P5.10
Operation alt., P2
On
P5.11
Operation alt., P3
Off
P8.1
Add. heat timer
60 minutes
P8.3.1
Time delay SV1
30 minutes
P8.3.2
Time delay for stop boiler
60 minutes
P8.3.6
Setting of SV1 runtime
1 minute
P1.1
Temp. incr. / decr.
4
P1.2
Temp. fine-tune
0ºC
P1.3
Heat curve adjustm.
0ºC
P1.4
Heat curve. hysteresis
5ºC
P1.5
Mix. valve incr/decr
4
P1.6
Mix. valve fine-tune
0ºC
P1.7
Mix. valve curve adjustm.
0ºC
P1.8
Mix. valve curve neut. zone
3ºC
P1.9
Mix. valve curve max. temp.
60ºC
P1.10
Room temperature
20ºC
P1.11
Room sensor influence
5
P1.12
Holiday function
0 days
P1.13
Remote control temperature not active
P1.14
Summer disconnection
18ºC
P1.16
Return thermostat stop
48ºC
P1.17
Return thermostat hyster.
5ºC
P2.1
Extra DHW
0 hours
P2.2
DHW peak interval
not active
Technical information
Table of factory settings
The table shows the factory settings of all the settings that can be changed by the installer.
Important points to check
During the first period after commissioning you should pay special attention to the pressure levels in
the heating system and heat transfer circuit. It might need filling up.
The factory setting of the motor cutout is based on a value during hot water charging and a stable
voltage. Because of the fluctuating voltages on the mains supply the recommended settings are not
always suitable and can therefore need adjusting from time to time. This is best achieved using a clip-
on ammeter during hot water operation.
For the heat pump to perform at its best, it is important to check the flow on the hot and cold side of
the heat pump. Usually, the heat transfer fluid pumps each have a speed selector switch. These must
be set correctly for the pressure drop in the systems. A recommended temperature difference over
the heat pump on the cold side is between 2-3°C and on the hot side between 7-10°C. You can
check this with the help of the sensor temperatures in line three of the control panel.
It is also important that the flow in the radiator system exceeds the flow across the heat pump. If this
is not the case, the heat pump flow goes back via the bypass to the heat pump return, which may
cause the heat pump to trip for high return temperature. The flow through the radiator system must
be high enough to ensure that the
entire
surface of the radiators is kept hot. This maximises the heat-
radiating surface and so keeps down the flow temperature from the heat pump.
After testing, vent the system again and top up with cold water if necessary.
Содержание D40
Страница 2: ...2 ...
Страница 64: ...64 Service log Only to be filled in by an authorised person Date Work done Company Initials ...
Страница 65: ...65 Notes ...
Страница 66: ...IVT Industrier AB Sweden www ivt se mailbox ivt se ...