You can shorten the time for restarting the heatpump here.
If there is a need for heating or hot water the heat pump
starts within 20 seconds. The settings must be repeated
each time you requirequick restart.
Selecting external control of heat pump, additional heat and
hot water charging. When the external inlet on Rego 600 is
short-circuited you can make the following choices:
0: No effect (factory setting).
1: HP, additional heat and hot water stop.
2: HP no effect, additional and hot water stop (this position
must not be chosen in operating mode C).
3: HP and hot water no effect, additional heat stops.
4: HP and additional heat no effect, hot water stops (this
position must not be chosen in operating mode C).
Note that if you choose any of the above alternatives you
cannot use any of the functions in 1.13 (remote control
heating).
You choose language in display 5.8. Svenska is the factory
setting.
Here you can choose to always have the heat transfer fluid
pump in operation or start and stop with compressor.
Continuous operation is the factory setting. This choice is
not available in operating mode C for technical reasons.
The heat transfer fluid pump should normally always start
and stop with the compressor. 5.11 you can choose to let it
go in continuous operation or during e.g. use of natural
cooling. Factory setting is start and stop with compressor.
Display 5.12 shows you the version number of Rego 600.
In display 5.13 you Ackn the extra sensors T3 (GT3), T4
(GT4) and T5 (GT5) that are connected externally. Using
Confirm, Rego 600 memorises the sensors used and the
heat pump then produces hot water when T3 (GT3) is
selected.
Commiss./Service
Connected extra
sensor in op. 5.13
Return Select
Commiss./Service
Display software
version number 5.12
Return Select
Commiss./Service
Select operation
alt. for P3 5.11
Return Select
Commiss./Service
Select operation
alt. for P2 5.10
Return Select
Commiss./Service
Selection of
language meny 5.8
Return Select
Commiss./Service
Fast restart
of heat pump 5.6
Return Select
Commiss./Service
Select external
controls 5.7
Return Select
If an accumulator tank is installed in the system, the heat transfer fluid pump G2 (P2) starts and stops
with the compressor. (Menu 5.10) Also see page. 56.