background image

2.7  Temperature control internal radiator curve

Only displays function that is enabled in Configuration 1. All other functions are 
hidden.

Main menu > Unit > Setpoints/Settings

Parameter

Value

Function

Outside

- - -

Current temperature used for control. Outdoor temperature

X2 OutdoorT. Setpoint

-64 – 99°C

Lowest outdoor temperature 2

Y2 Exp. Setpoint Temp.

-64 – 79°C

Highest supply line temperature 2

X3 OutdoorT. Setpoint

-50 – 25°C

Breaking point outdoor temperature 3

Y3 Exp. Setpoint Temp.

-0 – 130°C

Breaking point supply line temperature 3

X4 OutdoorT. Setpoint

-50 – 25°C

Breaking point outdoor temperature 4

Y4 Outdoor Temp Setpoint

-0 – 130°C

Breaking point supply line temperature 4

X5 OutdoorT. Setpoint

-50 – 25°C

Breaking point outdoor temperature 5

Y5 Exp. Setpoint Temp.

-0 – 130°C

Breaking point supply line temperature 5

X6 OutdoorT. Setpoint

-64 – 99°C

Highest outdoor temperature 6

Y6 Exp. Temp Setpoint

-64 – 99°C

Lowest supply line temperature 6

Current setpoint VP

- - -

Current calculated supply line setpoint

Supply lime Temp. VP

- - -

Current temperature used for control, supply line 
temperature.

Preconditions

Parameter settings

30

40

50

60

70

80

Y

X

Outdoor temp. 

[ºC]

Supply line temp. 

[ºC]

-30

20

0

-10

-20

10

EcoHeater
District heating

X6, Y6

X5, Y5

X4, Y4

X3, Y3

X2, Y2

Quick Start Manual for the EcoHeater Climatix control system
18710-6011 SMCX.151008.00EN

Page 14

Содержание EcoHeater Climatix

Страница 1: ...Control equipment EcoHeater Climatix Quick Start Manual Climatix Control Unit ...

Страница 2: ......

Страница 3: ...s and stops 12 2 7 Temperature control internal radiator curve 14 3 Alarm 15 3 1 General 15 3 2 Alarm list information 17 3 3 Alarm list 17 3 4 Alarm history 17 3 5 Alarm and history list settings 18 4 Commissioning of internal Modbus TCP 19 5 Save and restore commissioning factory settings 20 5 1 Save 20 5 2 Restore 20 Quick Start Manual for the EcoHeater Climatix control system 18710 6011 SMCX 1...

Страница 4: ...Quick Start Manual for the EcoHeater Climatix control system 18710 6011 SMCX 151008 00EN Page 2 ...

Страница 5: ...or to cancel edit in progress E Navigation and OK button Turn clockwise or anticlockwise to move down or up in the menus Press to enter a menu go to the next page or edit a value Turn to change value Keep pressed down to go straight to the login menu if the value you want to edit requires login C Display window Hand held unit Login To edit the most common parameters e g setpoints temperatures etc ...

Страница 6: ...ustment dial Press Return to previous page after you have gone to the main menu via the Info button Press B Alarm button Light emitting diode LED Off No alarm Flashing Alarm activated Constant light Alarm activated and acknowledged Press button to Return to most recent alarm Go to alarm list displays activated alarm and alarm history Go to alarm history Go to alarm settings Acknowledge and reset a...

Страница 7: ... black background when it is displayed The current value of the alternative is displayed in front of the navigation arrow Navigation Select the row Turn the adjustment dial Go to the underlying level Press the adjustment dial Act fan stage Off The alternative is also displayed against a black background when displayed in write protected mode The current value of the alternative is displayed Fan st...

Страница 8: ...ent dial Select or deselect value Press the adjustment dial Apply the new value Select Done Turn the adjustment dial Select Done Press the adjustment dial or Retain the old value and close the settings page Press the ESC button The scale displays the minimum and maximum values that can be set Change set value Change the value below the arrow Turn the adjustment dial Move the arrow to the left Turn...

Страница 9: ...set to automatic operation Go to the page for all settings for example alarm class for enabled manual alarm Auto mode No object is controlled manually or is disabled Manual mode At least one object is controlled manually or is disabled Enable manual alarm No Yes Enable alarm of Manual operation Manual No alarm Alarm enabled Enable comm test This function is not available Communication test This fu...

Страница 10: ...l program From BMS Auto Off Step 1 Step 2 Step 3 Displays control from BVMS only if Time control prog funct Step Temp The value can be set via the control unit even when communication is disabled Auto mode AHU can be switched in via time control program etc AHU switched off AHU operation in step 1 uses setpoint value 1 for analogue outputs AHU operation in step 2 uses setpoint value 2 for analogue...

Страница 11: ...l s 0 5000 Pa Depending on type of control Fan control type Direct or Dir var Current calculated fan setpoint Step 1 0 100 0 40 000 l s 0 5000 Pa Depending on type of control Fan control type Direct or Dir var Setpoint for step 1 Time control prog step 1 for controlled fans Step 2 0 100 0 40 000 l s 0 5000 Pa Depending on type of control Fan control type Direct or Dir var Setpoint for step 2 Time ...

Страница 12: ...ct set desired output Manual control changing to Active and lamp flashes Return Select Manual control Active and change to ZERO ZERO means that the output is controlled by the program s parameters and functions Active means that the output is set manually Lamp flashes when an output is controlled manually Reset by changing Active to ZERO or by selecting Main menu General functions Reset I O to Aut...

Страница 13: ...n accordance with schedule or selected mode for continuous operation Continuous operation No Step1 Step2 Step3 Continuous operation function switched off The AHU runs according to the time control program s schedule The AHU runs constantly on operating step 1 The AHU runs constantly on operating step 2 The AHU runs constantly on operating step 3 Monday Displays current control if current day is Mo...

Страница 14: ...r exceptions Main menu Unit Operating functions Time control program Calendar stops Main menu Unit Auxiliary Time prog output Calendar exceptions Parameter Value Function Current value Passive Active Shows whether a calendar time is enabled No calendar time enabled Calendar time enabled Select x Date Interval Weekday Passive Specification of exception type A certain day e g Friday A period e g hol...

Страница 15: ... exception days Start Date 00 End date 00 Warning This means that exceptions are always active The AHU is continuously in exception mode or switched off The times for weekday are applied Weekday Fr Every Friday is an exception day Weekday Fr Even Every Friday in even months February April June August etc is an exception day Weekday Warning This means that exceptions are always active The AHU is co...

Страница 16: ...int outdoor temperature 4 Y4 Outdoor Temp Setpoint 0 130 C Breaking point supply line temperature 4 X5 OutdoorT Setpoint 50 25 C Breaking point outdoor temperature 5 Y5 Exp Setpoint Temp 0 130 C Breaking point supply line temperature 5 X6 OutdoorT Setpoint 64 99 C Highest outdoor temperature 6 Y6 Exp Temp Setpoint 64 99 C Lowest supply line temperature 6 Current setpoint VP Current calculated supp...

Страница 17: ...alarm symbol in the built in control unit lights up Alarm reset Alarm list the alarm entry is removed History list the alarm entry is displayed as removed Procedure for alarm that releases values Active unconfirmed Active unconfirmed Normal LED flashes LED off Normal Confirm Alarm disappears LED lights continuously Alarm disappears Alarm occurs Procedure for alarm that retains values Inactive not ...

Страница 18: ...n Press alarm button Press alarm button Press alarm button Press alarm button Alarm list history settings Alarm LED lights continuously Alarm list Alarm history Detailed info Most recent alarm Alarm button function Quick Start Manual for the EcoHeater Climatix control system 18710 6011 SMCX 151008 00EN Page 16 ...

Страница 19: ...ent dial to display detailed information about the alarm Press the alarm button to display the list settings The list can contain up to 50 entries 3 3 Alarm history The following information about active and passive alarms is included in the alarm list Row 1 Number of alarms not yet reset Acknowledged Passive number Example Acknowledged Passive 14 Press control unit s adjustment dial to acknowledg...

Страница 20: ...us fault no fault Sort 2 Time Name Class Status Secondary sort criterion See sort order 1 Descending Passive Active Alarms sorted in ascending or descending order Ascending Descending Alarm history Reset Deletion of the history list Sort 1 Time Name Class Status Primary sort criterion See Alarm list Sort 2 Time Name Class Status Secondary sort criterion See Alarm list Descending Passive Active See...

Страница 21: ...or TCP IP NB Settings for TCP IP can also be viewed and changed here Main menu System summary Communication TCP IP Make sure that you change the TCP IP settings if the control unit is already connected to the Ethernet for any other purpose 5 Select DHCP normally Passive Active DHCP server issues addresses Passive IP address is fixed 6 Select Set IP Specify the control unit s IP address if DHCP is ...

Страница 22: ...oad RESTART The unit restarts on its own if the alternative is changed from HMI to Download or vice versa When the unit has restarted proceed to Main menu System summary Save Restore Insert the SD memory with the saved settings in the main unit s memory card reader Select Download param from SD Execute Full The saved settings on the SD card are downloaded to active current settings in the control ...

Страница 23: ...0 Q63 Q64 Q54 Q53 24 230V Q6 T 7 Q5 Q43 Q44 Q34 Q33 24 230V Q4 T 6 Q3 Q23 Q24 Q14 Q13 Q2 Q1 Y2 M Y1 T 3 24V 0V T 1 D2 M D1 T4 D3 D4 M D5 M X2 M X1 T4 24V 24V X3 X4 M X5 X6 X7 X8 M M Quick Start Manual for the EcoHeater Climatix control system 18710 6011 SMCX 151008 00EN Page 21 ...

Страница 24: ...IV Produkt AB Box 3103 SE 350 43 Växjö SWEDEN Phone 46 0 470 75 88 00 Fax 46 0 470 75 88 76 info ivprodukt se www ivprodukt se 18710 6011 SMCX 151008 00EN ...

Отзывы: