2.7 Temperature control internal radiator curve
Only displays function that is enabled in Configuration 1. All other functions are
hidden.
Main menu > Unit > Setpoints/Settings
Parameter
Value
Function
Outside
- - -
Current temperature used for control. Outdoor temperature
X2 OutdoorT. Setpoint
-64 – 99°C
Lowest outdoor temperature 2
Y2 Exp. Setpoint Temp.
-64 – 79°C
Highest supply line temperature 2
X3 OutdoorT. Setpoint
-50 – 25°C
Breaking point outdoor temperature 3
Y3 Exp. Setpoint Temp.
-0 – 130°C
Breaking point supply line temperature 3
X4 OutdoorT. Setpoint
-50 – 25°C
Breaking point outdoor temperature 4
Y4 Outdoor Temp Setpoint
-0 – 130°C
Breaking point supply line temperature 4
X5 OutdoorT. Setpoint
-50 – 25°C
Breaking point outdoor temperature 5
Y5 Exp. Setpoint Temp.
-0 – 130°C
Breaking point supply line temperature 5
X6 OutdoorT. Setpoint
-64 – 99°C
Highest outdoor temperature 6
Y6 Exp. Temp Setpoint
-64 – 99°C
Lowest supply line temperature 6
Current setpoint VP
- - -
Current calculated supply line setpoint
Supply lime Temp. VP
- - -
Current temperature used for control, supply line
temperature.
Preconditions
Parameter settings
30
40
50
60
70
80
Y
X
Outdoor temp.
[ºC]
Supply line temp.
[ºC]
-30
20
0
-10
-20
10
EcoHeater
District heating
X6, Y6
X5, Y5
X4, Y4
X3, Y3
X2, Y2
Quick Start Manual for the EcoHeater Climatix control system
18710-6011 SMCX.151008.00EN
Page 14