5.
Save and restore commissioning/factory
settings
After settings and adjustments have been made, parameters and settings should be
saved in both the internal memory in the Climatix control unit and in the SD memory
so that they can be restored after any loss of data.
5.1 Save
5.1.1 Commissioning settings
Main menu > System summary > Save/Restore >
Select
Save comm. settings > Execute
. Current settings are saved to the internal
memory in the main unit.
5.1.2 SD memory settings
Main menu > System summary > Save/Restore >
Insert an SD memory in the main unit’s memory card reader. Select
Save param. to
SD > Execute
. Current settings are saved to SD:
NB: Existing parameters on the SD card will be overwritten with the new ones.
5.2 Restore
5.2.1 Commissioning settings
Main menu > System summary > Save/Restore >
Select
Restore comm. settings. > Execute
. Most recently saved settings are
restored from the internal memory in the main unit to active current settings.
5.2.2 Settings from SD memory.
Main menu > Configuration > Configuration via Download
RESTART - The unit restarts on its own if the alternative is changed from
HMI
to
Download
or vice versa. When the unit has restarted, proceed to:
Main menu > System summary > Save/Restore >
Insert the SD memory with the saved settings in the main unit’s memory card reader.
Select
Download param. from SD > Execute Full
. The saved settings on the SD
card are downloaded to active current settings in the control unit. After this a restart
is required:
Main menu > System summary > Save/Restore > Restart
.
5.2.3 Restore factory settings
If you need to return to the settings with which the unit was delivered from the
factory, this is how to restore the factory settings:
Main menu > System summary > Save/Restore >
Select
Restore factory settings. > Execute.
The saved factory settings in the
internal memory are downloaded to active current settings in the control unit.
RESTART - The unit restarts itself once
Execute
has been selected.
After this automatic restart an additional restart should be performed:
Main menu > System summary > Save/Restore > Restart
.
Parameter settings
Parameter settings
Parameter settings
Parameter settings
Parameter settings
Quick Start Manual for the EcoHeater Climatix control system
18710-6011 SMCX.151008.00EN
Page 20