2.2 Operating mode
2.2.1 General
Function for setting and displaying all settings for current operating mode, i.e.
starting conditions, switch-off conditions and operating mode. The AHU can also
be controlled via the control unit.
None.
None.
Configuration in Configuration 1 and Configuration 2 specifies various methods of
switching on the AHU.
Main menu > Unit > Operating functions
Parameter
Value
Function
Current
–
Off
–
On
–
Damper motion
–
Fire
–
Stop
–
Start-up
Operating mode:
–
Switched off.
–
Comfort mode.
–
Fire damper test.
–
Fire mode (depending on parameter setting for
fire mode).
–
AHU stopped and blocked (regulator in start
phase, configuration not complete, alarm class
danger, emergency stop).
–
AHU’s start-up procedure enabled.
Schedule
–
Off
–
Step 1…Step 3
Displays current control for timer control program
(only if Timer control prog. funct. = Step).
Go to the page for setting parameters of time
control program.
From BMS
–
Auto.
–
Off
–
Step 1
–
Step 2
–
Step 3
Displays control from BVMS (only if Time control
prog. funct. <> Step+Temp). The value can be set
via the control unit even when communication is
disabled.
–
Auto mode: AHU can be switched in via time
control program, etc.
–
AHU switched off.
–
AHU operation in step 1 (uses setpoint value 1
for analogue outputs).
–
AHU operation in step 2 (uses setpoint value 2
for analogue outputs).
–
AHU operation in step 3 (uses setpoint value 3
for analogue outputs).
External control
–
Auto.
–
Off
–
Step 1
–
Step 2
–
Step 3
Displays current control from external control.
–
Auto mode: AHU can be switched on via time
control program, timer, etc.
–
AHU switched off.
–
AHU operation in step 1 (uses setpoint value 1
for analogue outputs).
–
AHU operation in step 2 (uses setpoint value 2
for analogue outputs).
–
AHU operation in step 3 (uses setpoint value 3
for analogue outputs).
Power up delay
0…36000 [s]
Delayed start after restart of regulator.
Purpose
Preconditions
Parameter settings
View/settings
Quick Start Manual for the EcoHeater Climatix control system
18710-6011 SMCX.151008.00EN