![IV Produkt EcoHeater Climatix Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/iv-produkt/ecoheater-climatix/ecoheater-climatix_quick-start-manual_2096947013.webp)
2.3 Detailed pages for time control program
This section describes functions and setting for time control programs and calendars.
Possible values vary, depending on the configuration. This is done in Configuration 1:
Main menu > Configuration > Configuration 1 > Time control prog. funct.
Main menu > Configuration > Configuration 1 > Time control prog. step.
Off or On can be specified for the aux time control program:
Main menu > Configuration > Configuration 2 > Aux. time control prog.
If no object with a higher priority (for example Manual control <> Auto) is enabled,
the AHU can be switched off or step-changed (for frequency-controlled fans to the
specified setpoint) via the time control program. A maximum of six switching times
per week may be specified.
Calendar stop ignores calendar exceptions, which in turn ignores the normal time
control program (only in operating mode). Up to ten periods or exception days can
be specified for each calendar.
2.4 Weekly schedule
Quick menu > Time control program > Schedule
Main menu > Unit > Operating functions > Time control program > Schedule
Parameter
Value
Function
Current value
---
Switching in accordance with schedule or selected
mode for continuous operation.
Continuous operation
No
Step1
Step2
Step3
Continuous operation
function switched off. The
AHU runs according to the time control program’s
schedule.
The AHU runs constantly on operating step 1.
The AHU runs constantly on operating step 2.
The AHU runs constantly on operating step 3.
Monday
Displays current control if current day is Monday. The
latest time that can be specified for a day is 23:59.
Go to daily switching schedule for Mondays.
Copy schedule
Mon to
Tue-Fri
Tue-Sun
Copies times for time control program from Monday
to Tuesday-Friday:
Passive (no copying).
Copying starts Return to display screen.
Copying starts Return to display screen.
Tuesday
Same function as for Monday.
...
...
Sunday
Same function as for Monday.
Exception
Displays current control if current day is an exception
day. Go to daily switching schedule for exception days.
Period:Start
(
Technical authorisation level
only.)
Start date for weekly schedule.
*,* *.00 means that the weekly schedule is always
enabled. ---> Enable weekly schedule.
Period:End
(
Technical authorisation level
only.)
Start date and start time for disabling weekly
schedule.
Aux time control program
Function
Parameter
Quick Start Manual for the EcoHeater Climatix control system
18710-6011 SMCX.151008.00EN
Page 11