CALIBRATION AND ADJUSTMENTS 

 

For adjustment and/or calibration verification, use the following 
calibration procedure: 
 

1.  Connect the required air supply pressure (25 psig for the 

GT18 and GT28, 35 psig for all others) to the inlet of the 
transducer, and a pressure gauge to the outlet. 

2.  Connect the electrical input and set the input signal to the 

0% value (e.g. 4 mA for a direct acting 4-20 mA unit). 

3.  Observe the output pressure.  Adjust if necessary by 

turning the external zero adjust screw located under the 
cap near the output pressure connection. 

4.  Increase the electrical input signal to the 100% value (e.g. 

20 mA for a direct acting 4-20 mA unit). 

5.  Observe the output pressure.  If adjustment is necessary, 

remove the cover cap and adjust the range potentiometer 
on the circuit board to obtain the required output. 

6.  The zero and range adjustments are interactive.  After 

adjusting the range potentiometer it will be necessary to 
recheck the zero.  Repeat steps 2 through 5 until both 
endpoints are at the required values. 

 
 

MAINTENANCE 

 

Under normal conditions, no maintenance should be required.  If 
disassembly is necessary, refer to PNEUMATIC 
TROUBLESHOOTING section of this document.  It is important 
that clean, dry air be supplied to the unit at all times.  An ITT 
Conoflow FR95 series Airpak (filter regulator) or equivalent 
filtered air supply can be used to supply this I/P transducer 
 
For pressure relay equipped models (GT28, GT48, or GT68) 
periodically inspect the diaphragm assembly to see if the 
diaphragm assembly shows signs of wear.  To inspect, remove 
the six (6) machine screws from the relay.   While the relay is 
disassembled from the I/P transducer, check freedom of 
movement of the relay valve, and remove any foreign matter 
which may have accumulated.  When reassembling the relay, be 
sure to properly orient the relay body to align the feed hole from 
the inlet port to the fixed orifice in the housing cap.  Tighten the 
six (6) machine screws to 24 in-lb. 
 
For replacement components, contact the factory with the full 
model number and serial number of the product that parts are 
required for. 
 
 
 
 
 
 
 
 
 
 
 
 

TROUBLESHOOTING 

 

PNEUMATIC 

 

1.  Check supply pressure.  It should be constant 25 psig 

(172 kPa) for the GT18 or GT 28 models, or a constant 35 
psig (241 kPa) for all other models. 

2.  Make sure that tubing connections are tight. 
3.  Check zero and span calibration as previously outlined. 
4.  Check to see if housing body screen or flame arrestor (XP 

version) is obstructed. 

5.  If disassembly is necessary, it must be done in a clean 

work area.  Should foreign debris become lodged between 
the coil assembly and the magnet assembly, a malfunction 
may occur.  Removal of the magnet assembly will destroy 
the calibration of the nozzle and balance beam 
relationship. 

6.  If resonance (humming) is experienced, check outlet 

piping to be sure it meets the minimum requirements 
specified under INSTALLATION. 

 

ELECTRICAL 

 

1.  Check to see that the input signal leads are connected to 

proper terminals (see ELECTRICAL CONNECTION 
section). 

2.  Make sure there are no loose wires at terminal or solder 

connections. 

3.  Some field calibrators may not be able to supply sufficient 

current to this transducer.  Verify the input DC mA signal 
using a digital ammeter. 

4.  Check input impedance by connecting an ohm meter to 

terminals 1 and 2.  In making any resistance tests, the 
input signal wires from the controller (mA source) must be 
disconnected.  Nominal total input impedance of the 4-20 
mA unit is 145 ohms.  Nominal total input impedance of 
the 10-50 mA unit is 60 ohms.  Do not change the setting 
of the range adjust potentiometer on the printed circuit 
board when performing input impedance test. 

5.  A measure of resistance between any terminal of the 

transducer and the external case should indicate an 
“open” circuit.  If resistance is indicated, coil windings or 
the leads to the voice coil may be touching the case.  
Further checks must then be made. 

6.  Remove housing from the transducer and disconnect the 

coil lead plug from the circuit board.  Check the 
impedance of the coil.  Nominal impedance is 
approximately 150 ohms.   
 

 

EXPLOSIONPROOF MODEL INFORMATION 

 

FM Approvals lists the explosionproof model as 
 
XP / I / 1 / BCD / T6 Ta = 60°C 
DIP / II / 1 / EFG / T6 Ta = 60°C 
 

 

 

 