Operation: CP1SD/T/L Version
82
CENTRON® Polyphase Meter Technical Reference Guide
Phase A Display
(Left Element)
Phase B Display
(Center Element)
Phase C Display
(Right Element)
%TDD I
0.010
0.500
0.500
Diagnostic
Counters
d1
0 d2
0 d3
0
d4
0 d5A
0 d5B
0
d5C
0 d5T
0 d6
1
The snapshot data indicates that there was harmonic distortion on Vb. Also note that the
diagnostic counter d6 has incremented to 1.
Testing, Troubleshooting, and Maintenance
This section provides information and instructions to help you test and maintain the
CENTRON Polyphase meter. Topics covered include:
Visual indicators
Energy testing
Demand testing
Recommended testing procedures
TOU schedule testing
Field testing
Troubleshooting (fatal and non-fatal errors)
Maintenance
Visual Indicators
The Infrared Test LED, as well as several other annunciators, assist you in testing and
troubleshooting the CENTRON Polyphase meter.
Infrared Test LED
The meter is equipped with an Infrared (IR) Test Light Emitting Diode (LED) for testing
meter accuracy; the LED is located at the top of the meter. The pulse weight represented by
the LED is programmable through the PC-PRO+ Advanced programming software for a
CP1SDTL meter. The programming software allows a different pulse weight value for the
LED in the following display modes: Normal, Alternate, Test, and Test Alternate. The meter
can be programmed to drive the Test LED with a variety of energy values, depending upon
the energy quantities selected in the configuration.
Annunciators
The CENTRON Polyphase meter is equipped with a variety of annunciators for a more
meaningful display.