Operation: CP1SD/T/L Version
CENTRON® Polyphase Meter Technical Reference Guide
97
Register Board not Properly Installed in Upper Housing
—Verify that the Register
board is fully engaged with the inner cover.
Switch or Electronic Failure
—Return meter for repair.
Diagnostic 1 Condition Incorrectly Active
Verify that meter determined the correct service type.
Diagnostic 2, 3, or 4 Condition Incorrectly Active
Verify that thresholds are not set too tight.
Counters Are Too High
Verify that thresholds are not set too tight.
Maintenance
Preventive Maintenance
No scheduled or preventive maintenance (other than battery replacement for TOU/Load
Profile versions) is necessary for the CENTRON Polyphase meter.
Line potential may exist on the battery terminals. Follow these
precautions:
•
Never short-circuit batteries (such as by measuring current
capability with an ammeter).
•
Do not recharge batteries.
•
Do not store or transport batteries in metal or other
electrically conductive containers.
•
Keep batteries separated. If stored in a container where
they can contact each other, face them in the same
direction to prevent short circuits.
•
Do not operate batteries at temperatures above 85°C
(185°F).
•
Dispose of batteries where they will not be punctured,
crushed, or incinerated.
•
Discard the battery using proper hazardous waste
procedures.
Corrective Maintenance
Because of the high level of integrated packaging and surface-mount components, on-board
component repairs are not recommended. The entire meter should be returned to Itron, Inc.
Customer Service for repair.