![ITRON CENTRON CP1S Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/itron/centron-cp1s/centron-cp1s_technical-reference-manual_2096036076.webp)
Operation: CP1SD/T/L Version
CENTRON® Polyphase Meter Technical Reference Guide
63
The PC-PRO+ Advanced software lets the user retrieve Toolbox information (the same
information available by accessing the display list through the use of a magnet and magnetic
switch) on an instantaneous basis with a graphical vector diagram.
To best understand the values on the Toolbox display, one should graphically plot this
information. Before starting to manually plot the Toolbox
data, two basic definitions must
be understood about the SiteScan system.
Definition 1:
The per-phase information displayed in the Toolbox
Mode is
referenced to the internal voltage and current sensors of the meter.
The meter will designate each phase by the elements. The table
below defines each element.
Phase Notation in Display
Element Used in Meter
Defined Phase
Phase Notation in Toolbox Display
Left-hand Element
Phase A
PhA
Center Element
Phase B
PhB
Right-hand Element
Phase C
PhC
The figure below shows how the wiring of each element determines the phase notation used
by the meter. (socket view)
I
A
I
B
I
C
V
A
V
B
V
C
N
Form 9S
Form 16S
I
A
I
B
I
C
V
A
V
B
V
C
N
Figure 25: Toolbox Phase Notation for Form 9S and 16S CENTRON Polyphase Meters