CURRENT REVERSAL (PHASE 1)
Self-healing
Change of direction of current flow on phase 1
CURRENT REVERSAL (PHASE 2)
Self-healing
Change of direction of current flow on phase 2
CURRENT REVERSAL (PHASE 3)
Self-healing
Change of direction of current flow on phase 3
TEMPERATURE
Self-healing
Meter temperature greater than threshold
VOLTAGE CUT (PHASE 1)
Self-healing
Voltage cut on phase 1 longer than threshold
VOLTAGE CUT (PHASE 2)
Self-healing
Voltage cut on phase 2 longer than threshold
VOLTAGE CUT (PHASE 3)
Self-healing
Voltage cut on phase 3 longer than threshold
VOLTAGE SAG (PHASE 1)
Self-healing
Voltage sag on phase 1 longer than threshold
VOLTAGE SAG (PHASE 2)
Self-healing
Voltage sag on phase 2 longer than threshold
VOLTAGE SAG (PHASE 3)
Self-healing
Voltage sag on phase 3 longer than threshold
VOLTAGE SWELL (PHASE 1)
Self-healing
Voltage swell on phase 1 longer than threshold
VOLTAGE SWELL (PHASE 2)
Self-healing
Voltage swell on phase 2 longer than threshold
VOLTAGE SWELL (PHASE 3)
Self-healing
Voltage swell on phase 3 longer than threshold
BATTERY LOW ALARM
Trapped
RTC battery voltage level less than threshold
(
see note 5 below
)
RWP BATTERY LOW
NO BATTERY ALARM
MAGNET ATTACK
EXCESS DEMAND
Self-healing
Demand over threshold detected
COMMUNICATIONS ERROR
Fatal alarm
Type
Description
INTERNAL RAM ERROR
Trapped
Permanent checksum error in internal RAM
EXTERNAL RAM ERROR
Trapped
Permanent checksum error in external RAM
INTERNAL PROGRAM MEMORY ERROR
Trapped
Permanent checksum error in internal code
EXTERNAL PROGRAM MEMORY ERROR
Trapped
Permanent checksum error in external code
Note
Alarm(s)
Comment
1
WATCHDOG ACTIVITY
NON VOLATILE MEMORY NON
FATAL ERROR
When these non-fatal alarms are detected, the meter uses the
previous 4 hours backup values.
It is recommended you remove/replace the meter, or at least erase
the fault with the support software and investigate the situation.
2
EXTERNAL CLOCK
INCOHERENCE
A non-fatal alarm, where the RTC chip does not accept external
programming. If it occurs only once, it has little effect on the meters
time management.
Содержание ACE6000
Страница 1: ...ACE6000 User Guide...
Страница 6: ...ACE6000 User Guide 4...
Страница 8: ...ACE6000 User Guide 6...
Страница 12: ...ACE6000 User Guide 10...
Страница 14: ...ACE6000 User Guide 12...
Страница 22: ...ACE6000 User Guide 20...
Страница 42: ...ACE6000 User Guide 40...
Страница 80: ...ACE6000 User Guide 78...