10.6.
Cabling
Main terminal wiring
The main terminal is the same design and specification for both Direct and Transformer connection meter types.
Terminal
Function
PH1
Terminal
Function
PH2
Terminal
Function
PH3
Terminal
Function
1
I1 in
4
I2 in
7
I3 in
10/11
Neutral in
2
U1 in
5
U2 in
8
U3 in
12
Neutral out
3
I1 out
6
I2 out
9
I3 out
Main terminal specification
Terminal type
Clamp screws
Cable diameter (max)
Meter type
Voltage
2 x M3
3.2mm
Transformer only
Current
2 x M6
8mm
Direct and Transformer
The meter can be configured for both 3 and 4 wire cabling, as shown in the following topics.
Note:
All examples show three-phase wiring.