TROUBLE-SHOOTING TABLES
PROBLEM CAUSE
&
REMEDY
The generator does not start
Check:
(red phase LED OFF)
- correct electrical connections - if the environmental thermostat is
fitted, make sure that it is not set too low.
The fan does not start
Check:
(red phase LED ON)
- motor power supply cable - safety fuse F1 - fuel oil pump: if ripped
replace
The fan starts but there is no
- Check the fuel level
combustion (the RESET - Make sure that the fuel oil filter is not clogged
push-button LED comes ON
- Make sure that the nozzle is not obstructed
after a few seconds)
- Make sure that no air enters the fuel circuit: make sure that the filter
cup is properly tightened and the seal ring is correctly positioned in its
seat
- Dirty photo sensitive cell: remove from support and clean
- Check the integrity of the plastic joint connecting the motor and the
fuel pump: if broken, replace
- Flame control system faulty: replace
- Make sure there is a spark between the electrodes. If this is not the
case, check the position of the electrodes, their integrity and the
status of the high voltage cables. Make sure that he transformer is
not burnt out.
The unit overheats during
- Excess flow of fuel caused by nozzle wear or installation of a nozzle
normal operation
having different features than the original - Poor flow of air caused by
faulty setting of combustion head fins - Obstructions in the ventilation
air route.
When the unit is switched off using
- Cooling thermostat faulty. Replace
the main switch or the environment
thermostat, the fan does not operate
and the generator overheats
The unit discharges lightcoloured fumes - Excess air or poor fuel - Impurities in the fuel circuit: clean the tank,
the filer and the ducts. Change the fuel - Air adjustment modified:
return the fins to their original positions.
The unit discharges dark fumes
- Air defect or excess fuel, caused by:
- clogged or nonconforming nozzle: replace.
The unit discharges dark fumes
- modified fuel pressure
- flame turbo obstructed: clean
- air adjustment modified: return the fins to their original positions.
Never halt the generator simply by removing the power plug.
This would exclude post-cooling. Never change the fuel oil pump pressure setting. This would
modify all combustion features. When replacing the nozzle, use a spare with an identical
capacity to the nozzle fitted by the manufacturer
Содержание D 15 PV
Страница 70: ...1 RU 1 INDIRECT DIRECT 2 2 2 1 3 10 2 2 o DIRECT...
Страница 71: ...2 RU 3 30 2 0 003 17 3 DIRECT INDIRECT INDIRECT DIRECT only for INDIRECT generators IP 44...
Страница 72: ...3 RU 4 INDIRECT DIRECT 4 1 30 1 5 2 10 2 5 2 10 30 4 2 INDIRECT 120 150 MIZAR...
Страница 73: ...4 RU 5 5 1 ON RESET 5 2 OFF 5 3 AUT reset 10 reset SATRONIC DKO 970 6...
Страница 74: ...5 RU 7 8 10 3 300...
Страница 75: ...6 RU 8 RESET...
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 94: ......
Страница 95: ......