9. Product description
The I/O module I/O-04HD-230V-16A has been designed for appli-
cations where manual intervention is necessary, or where the status
of the relays must be kept in the event of a BUS or voltage failure. 4
circuits with a maximum of 230V/16A can be switched. As inputs 4
optocoupler inputs 230V on a common reference potential are avai-
Inputs / Outputs
• 4 relay outputs 230V/16A with manual actuation lever
• 4 optocoupler inputs 230V (1 phase!)
Function displays
• 1 red LED indicates the operating voltage
• 1 flashing yellow LED indicates the communication with the master via subnet
• 4 green LEDs indicate the output states (parameterizable)
• 4 yellow LEDs indicate the input states
Connections
• 1 connection for the subnet (BUS A and B, RS-485)
• 1 connection for the operating voltage (Ub, 0V)
• 4 outputs
• 4 inputs (on a common reference terminal)
• 2 P-COM connections (subnet and operating voltage)
Design
• DIN rail mounted plastic housing light grey, snap-on on 35mm DIN rail, 6 HP
Special function DIP switch 1 = Emergency operation
• Switch „OFF“ = BUS operation
• Switch „ON“ = Emergency operation
lable. All inputs and outputs can be parameterized in the module for
various functions and are freely programmable in the functions via
the ISYGLT ProgramDesigner software. To protect the module from
dust and unwanted operation, it is closed with a transparent cover. A
screwdriver is required for manual operation.
•
The output relays can also be switched manually without programming (commissioning, service, maintenance...)
•
The relay position is maintained even if the supply voltage is interrupted.
•
Each individual output of the emergency module can be parameterized for the operating modes BUS operation, BUS failure, emergency
operation (DIP1 ON).
•
The feedback LEDs can indicate the status of the inputs or the outputs.
•
Due to the extensive parameter setting options, the module can also be used as a stand-alone module.