Earthcore Industries
MAGNUM
Series Fireplace
Attach the elbow to the chimney pipe, support or
other part. Using the offset chart, add chimney sections
between elbows. A Support Band or plumbers strap is
required for every 4 foot interval between elbows to
support the load.
(Figure 34)
Attach the upper elbow
to bring the chimney back to vertical. See
TABLE 2
and
(
Figure 35)
for offset combinations. 2 offsets (4 elbows)
maximum.
9.
For chase enclosures, install the chase top cover
(supplied by others) to the chase enclosure. Cut a hole
in the chase top cover the same diameter as the base
of the cone on the flashing. Attach the Flashing to the
top of the chase cover, sealing with a non-hardening
waterproof sealant. Secure in place with screws or rivets.
(Figure 36)
10.
Attach the storm collar around the chimney above the
screen of the flashing. Secure in place with the locking
tab and button. Seal around the storm collar with a non-
hardening waterproof sealant. Attach the Termination
Cap to the chimney by sliding the male to female joint
connection together and secure in place with four (4)
sheet metal screws provided.
(Figure 37)
11.
Termination:
NFPA 211, “Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel-Burning Appliances”,
states that chimneys shall extend at least three feet
above the highest point where it passes through the roof
of a building, and at least two feet higher than any portion
of a building within ten feet.
(Figure 38)
If the horizontal distance from the chimney edge
to the peak of the roof is greater than 10', a chimney
height reference point is established on the roof surface
10' horizontally from the chimney edge. The top of the
chimney (point where exhaust gases exit) must be at least
2' above this reference point. In all cases the chimney
must terminate a minimum of 3' above the highest point
of the roof opening.
The ten foot rule is necessary in the interest of
safety and does not ensure smoke free operation. Trees,
building, adjoining rooflines, adverse wind conditions,
etc., may require a taller chimney should a smoking
problem exist.
ECO-STEEL/ECO-STEEL+ Metal Chimney Installation
Screw Or
Rivet Straps
To Flashing
Chase
Cover
(Supplied by
Others)
Screw
Or Rivet
To Chase
Cover
Apply Sealant
Screw to
Chase
Chase
Chimney
Self-Tapping
Screws
Apply
Sealant
Flashing
Storm Collar
Termination
3 Feet Minimum
Above Roofline
2 Feet Above Any
Point Within
10 Feet Horizontally
FIGURE 36
FIGURE 37
FIGURE 38