Earthcore Industries

MAGNUM   Series Fireplace 

ECO-STEEL/ECO-STEEL+ General Information

 

The ECO-Steel Air-Cooled and Insulated Chimney 

is intended for use on Isokern fireplaces. Do not use 

with forced draft or positive-pressure appliances. The 

ECO-Steel Air-Cooled and Insulated chimney system is 

designed to extend a maximum of 60 feet vertically and 

with a maximum of one (2) offset (four elbows total) of 

up to 30° from vertical. Contact Local Building or Fire 

Officials about restrictions and installation inspection 

in your area. These instructions must be followed in all 

details and failure to do so may result in a hazardous 

installation. 

 

ECO-STEEL Air-Cooled Chimney is not designed for 

use on products that operate at continuous temperatures 

in excess of 1000°F. The following instructions are a 

general representation for ECO-STEEL & ECO-STEEL+ 

Chimney Installation. 

 

Creosote and Soot – Formation and Need for Removal

When wood is burned slowly, it produces tar and other 

organic vapors, which combine with expelled moisture 

to create creosote. The creosote vapors condense in the 

relatively cool chimney flue of the slow burning fire. As a 

result, creosote residue accumulates on the flue lining. 

When ignited, the creosote makes an extremely hot fire. 

The chimney should be inspected at least once every 

two (2) months during the heating season to determine 

if a creosote or soot buildup has occurred. If creosote or 

soot has accumulated, it should be removed to reduce 

the risk of chimney fire.

  Chimneys must be installed so that access is 

provided for inspection and cleaning.

 

Never fill any required clearance space with insulation 

or any other building materials surrounding the chimney.

 

Do not use a fireplace for food grilling. Grease from 

foods can collect in chimney causing fireplace to become 

a potential fire hazard.

 

Some chemical Chimney cleaners can be harmful 

to the chimney. These cause accelerated oxidation or 

corrosion. If chemical cleaners are used, they must be 

non-corrosive in nature. If a brush is used, it must be 

of proper size with plastic bristles. Have your chimney 

cleaned by a professional, certified chimney sweep.

 

If a flue fire occurs, close all possible air inlets, and 

call your Fire Department. Do not use the chimney again 

until it has been inspected by a Certified Chimney Sweep 

for possible damage.

  Exterior metal parts, with exception of the top 

portion of the chimney cap, can be painted with a high 

temperature rust proof paint. Wash the metal surface 

with a vinegar and water solution to remove any residue 

before painting. Painting the chimney will help to increase 

chimney life.

 

Earthcore assumes no liability for structural damage 

or roof contamination as the result of creosote formation. 

It is the owner’s responsibility to comply with inspection 

and cleaning requirements as described in these 

instructions, and those of the appliance manufacturer.

  Interior chimneys shall be enclosed where they 

extend through closets, storage areas, occupied spaces, 

or anywhere the surface of the chimney could be 

contacted by persons or combustible materials. 

The air 

space between the outer wall of the chimney and the 
enclosure shall not be less than 2 inches.

  WARNING: Do not place any type of insulation 

or other materials in the required clearance spaces 

surrounding the chimney assembly.

 

Except for installation in one or two family dwellings, 

a factory built chimney that extends through any zone 

above that on which the connected appliance is located is 

to be provided with an enclosure having a fire resistance 

rating equal to or greater than that of the floor or roof 

assemblies through which it passes.

 

In cold climates, chimneys mounted on an outside 

wall should be enclosed in a chase. Exterior chases 

reduce condensation, creosote formation and enhance 

draft.

 

Proper planning for your ECO-STEEL or ECO-STEEL 

+ Air-Cooled Chimney installation will result in greater 

safety, efficiency and convenience. You must use 

only ECO-STEEL & ECO-STEEL + Chimney parts and 

components to maintain a listed chimney system. Do 

not mix parts or try to match with other products or use 

improvised solutions.

 

Install your Isokern fireplace as described in this 

installation manual and maintain all required clearances.

 

Connect only one fireplace per chimney. Follow the 

fireplace safety manual for maximum efficiency and 

safety. Do not over fire. Any damage to the fireplace or 

chimney can possibly void the warranty.

 

Do not burn driftwood, plastic, or chemically treated 

wood such as railroad ties. They are corrosive to your 

chimney system. 

Note:

 For ECO-STEEL/ECO-STEEL+ installation see 

pages 35-39. For Duravent installation visit website 

earthcore.co. to download pdf.

A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS 
FAILURE TO MAINTAIN REQUIRED CLEARANCE (AIR 
SPACES) TO COMBUSTIBLE MATERIAL*. MINIMUM 
CLEARANCE FOR 13” DIAMETER AIR-COOLED  AND 
INSULATED CHIMNEY IS TWO (2) INCHES. IT IS OF 
UTMOST IMPORTANCE THAT THIS CHIMNEY IS 
INSTALLED ONLY IN ACCORDANCE WITH THESE 
INSTRUCTIONS.

Содержание MAGNUM 82084

Страница 1: ...MAGNUM Series Fireplace in a manufactured home or mobile home or recreational vehicle Important This manual contains assembly rules installation steps guidelines use and maintenance instructions for...

Страница 2: ...08 28 Assembled MAGNUM 120 29 2 Earthcore Industries MAGNUM Series Fireplace Table of Contents ECO STEEL ECO STEEL Metal Chimney Flue 30 Components List ECO STEEL ECO STEEL Metal Chimney Flue 31 Compo...

Страница 3: ...the Isokern fireplace ECO STEEL ECO STEEL chimney system for an indoor application is 18 0 when the chimney is straight and 21 0 when a chimney is offset Earthcore Industries MAGNUM Series Fireplace G...

Страница 4: ...nces Always maintain the stated minimum clearances to combustible materials Do not violate any specific installation requirements SEISMIC CODE If you are installing the MAGNUM Series Fireplace in a lo...

Страница 5: ...with the MAGNUM Series fireplace system unless written authorization is given by Earthcore Earthcore Industries MAGNUM Series Fireplace Safety Instructions Industries LLC Failure to heed this warning...

Страница 6: ...the appliance Toddlers youngchildrenandothersmaybesusceptibletoaccidental contact burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to the firepl...

Страница 7: ...nning installation contact your local building official to determine the need to obtain a permit PFS Magnum Listing Label NA PFS EARTHCORE INDUSTRIES MADE IN USA CHESAPEAKE VA 23323 HEADQUARTERS JACKS...

Страница 8: ...1 2 A A 710 27 15 16 681 5 26 13 16 533 5 21 640 25 3 16 70 2 3 4 272 5 10 3 4 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 710 27 15 16 533 5 21 681 5 26 13 16 345 13 9 16 FLUE OUTLET 2110 5 83 1...

Страница 9: ...MAGNUM Damper Beam Qty 2 75 Isokern MAGNUM Damper Beam Qty 2 25 4 26 25 26 4 35 8 77 8 8 38 77 8 36 4 16 18 Isokern MAGNUM Smoke Dome Qty 2 Isokern MAGNUM Backwall Qty 5 160 Isokern MAGNUM Base Plate...

Страница 10: ...5 16 517 20 3 8 571 5 22 1 2 571 22 1 2 571 5 22 1 2 517 20 3 8 640 25 3 16 70 2 3 4 272 5 10 3 4 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 710 27...

Страница 11: ...Damper Beam Qty 2 22 1 2 25 1 4 4 25 4 221 2 35 8 77 8 8 38 77 8 18 5 8 4 16 110 SMOKE DOME MIDDLE SMALL 8 MAGNUM QTY 2 18 5 8 4 16 110 Isokern MAGNUM Smoke Dome Qty 2 Isokern MAGNUM Backwall Qty 5 1...

Страница 12: ...666 5 26 1 4 533 5 21 653 5 25 3 4 533 5 21 666 5 26 1 4 640 25 3 16 70 2 3 4 272 5 10 3 4 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 710 27 15 16...

Страница 13: ...sokern MAGNUM Backwall Qty 5 73 Isokern MAGNUM Backwall Qty 5 114 Isokern MAGNUM Smoke Dome Qty 2 168 Isokern MAGNUM Damper Beam Middle Qty 2 114 SMOKE DOME MIDDLE LARGE 9 MAGNUM QTY 2 30 7 8 4 16 161...

Страница 14: ...679 5 26 3 4 645 25 3 8 679 5 26 3 4 670 5 26 3 8 640 25 1 4 70 2 3 4 272 5 10 3 4 345 13 5 8 FLUE OUTLET 345 13 5 8 FLUE OUTLET 345 13 5 8 FLUE OUTLET 345 13 5 8 FLUE OUTLET 3026 119 1 8 528 20 3 4 5...

Страница 15: ...Backwall Qty 5 73 Isokern MAGNUM Backwall Qty 5 116 Isokern MAGNUM Smoke Dome Qty 2 170 Isokern MAGNUM Damper Beam Middle Qty 2 116 SMOKE DOME MIDDLE LARGE 10 MAGNUM QTY 2 42 1 2 4 16 162 BACKWALL MID...

Страница 16: ...learances to combustible framing and to insulation are maintained throughout the construction of the project subsequent to the installation of the Isokern unit To avoid causing a fire resulting in dam...

Страница 17: ...de required non combustible hearth extension finish materials Figures 4 All MAGNUM Series fireplaces shall have hearth extensions of approved non combustible material such as brick tile or stone that...

Страница 18: ...s for off grade slabs must be concrete or steel and capable of supporting the slab Isokern unit and the chimney For multi floor and back to back installations proper weight computation on an individua...

Страница 19: ...f the Fireplace 4 Rough framing dimension for depth C allows for the required 1 clearance at the back of the Fireplace 29 1 2 is only for an interior wall as most exterior wall framing have insulation...

Страница 20: ...int as a sign of complete and proper sealing of the joint On broader contact surfaces it is advisable to apply several additional 1 2 beads of the Earthcore Adhesive to the area to assure proper seali...

Страница 21: ...d raised hearth height on the concrete support slab See page 18 When calculating raised hearth height be sure to allow for the three inch 3 thick base plate plus the one and one half inch 1 1 2 thick...

Страница 22: ...ox assembly for level by inserting a shim supplied with the unit between the lowest wall component and the top surface of the base plate Any gap created under the wall components during the Shim level...

Страница 23: ...it sits on Figure 20 The six 6 lintels when they are put together they will be equal to the width of the fireplace model that they serve Properly placed the lintel is to sit on top of the firebox back...

Страница 24: ...ont and rear smoke dome components Earthcore adhesive all contact surfaces thoroughly The smoke dome sloping sidewalls have a beveled bottom edge so that they will sit tight onto the flat top of the d...

Страница 25: ...oke dome sloping sidewalls have a beveled bottom edge so that they will sit tight onto the flat top of the damper beam assembly Figure 24 11 Set the top plates into position and Earthcore adhesive on...

Страница 26: ...ssembled MAGNUM 84 Part 79L Part 79R Part 34 Part 34 Part M94R Part 162 Part M96 Part 177 Part M90 Part M93 Part 191 Part 162 Part 162 Part 162 Part 17 Part 18 Part 16 Part 17 Part 112 Part 160 Part 1...

Страница 27: ...MAGNUM 96 Part 136 Part 36 Part 34 Part 34 Part M94R Part 162 Part 191 Part 36 Part M90 Part M91 Part M93 Part 162 Part 162 Part 162 Part 16 Part 17 Part 16 Part 17 Part 113 Part 160 Part 160 Part 73...

Страница 28: ...UM 108 Part 79L Part 177 Part 34 Part 34 Part M94R Part 161 Part M92 Part 177 Part M90 Part M92 Part 192 Part 161 Part 161 Part 161 Part 16 Part 16 Part 16 Part 16 Part 114 Part 72 Part 72 Part 73 Par...

Страница 29: ...rt 79R Part 34 Part 34 Part M94R Part 162 Part M93 Part 79L Part M90 Part M92 Part M96 Part 162 Part 162 Part 162 Part 16 Part 16 Part 16 Part 16 Part 116 Part 73 Part 73 Part 71 Part 71 Part 83 Part...

Страница 30: ...king tab design DURAVENT A lightweight venting solution created so each section connects securely together This versatile system has a 13 inner diameter and 16 outer diameter and is available in two o...

Страница 31: ...ated 30 Degree Offset Stainless Steel 13ACECO30OS 30 Degree Offset 13ACECOFC Chase Top Flashing 13ACECOSC Storm Collar 13NECOAP Insulated Anchor Plate w Damper Stainless Steel 13ACECO12 12 Chimney Sec...

Страница 32: ...OP13 WS ECOP13WS SS Wall Band ECOP13 CTC Chase Top Collar ECOP13AC E30 30 Degree Offset ECOP13 CTF Chase Top Flashing ECOP13 CTC Storm Collar ECOP13AC 12 12 Chimney Section ECOP13AC 18 18 Chimney Sect...

Страница 33: ...Chimney Section Stainless Steel Component Part Description ECOP13IN KAP Insulated Anchor Plate ECOP13IN KAPD Insulated Anchor Plate w Damper ECOP13IN E15K ECOP13IN E15KSS ECOP13IN E30K ECOP13IN E30KSS...

Страница 34: ...the chimney cap can be painted with a high temperature rust proof paint Wash the metal surface with a vinegar and water solution to remove any residue before painting Painting the chimney will help to...

Страница 35: ...amper plate in the closed horizontal position Determine and mark the position of the lintel hook The lintel hook should be mounted in a position so as to provide a small amount of tension in the sprin...

Страница 36: ...ectly above the opening below The cut opening must be 4 inches larger than the chimney s outside diameter to provide at least a 2 inch clearance all around the chimney The chimney must be centered in...

Страница 37: ...nails or screws per bracket A Support Band may be required by some fireplace manufacturers to keep the chimney vertical and help maintain clearances to combustibles within a chase Clamp the Support B...

Страница 38: ...8 Elbow Installation 15 and 30 elbows are provided to allow chimneys to avoid framing members or roof peaks A maximum of 30 from vertical is allowed and a total of two elbows for each chimney install...

Страница 39: ...ed Figure 37 11 Termination NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances states that chimneys shall extend at least three feet above the highest point where it pas...

Страница 40: ...when the fireplace is not in use It eliminates the need for glass doors opening up many new design options while allowing for a larger view area of the fire and a more natural look The system consists...

Страница 41: ...n air as directly as possible from the fireplace The duct cannot rise vertical higher than the finished opening of the firebox We recommend not to exceed twenty feet 20 of four inch 4 pipe If you requ...

Страница 42: ...h a damp sponge to remove dust and loose particles from the interior before installing firebrick Keep the fireplace damp while installing firebrick For Best Results 1 After wet sponged interior of fir...

Страница 43: ...stible finished facings are applied Flush Wall Finish Detail This alignment of firebrick application as shown below Figure 45 allows the firebrick lining to be in the same plane with the room s wall f...

Страница 44: ...projection Combustible projecting mantles up to twelve inches 12 of projection shall not be placed less than twenty four inches 24 from the top of the fireplace opening Combustible mantles which proje...

Страница 45: ...e vents properly upward through the chimney and doesn t create a downdraft that will push the smoke back out of the hearth The use of ECO STEEL ECO STEEL Chimney flue are the flue types for the MAGNUM...

Страница 46: ...Sidewall Cavity of Firebox Fill Cavity with f c 2000psi Concrete or Grout PROCEDURE 1 DRILL HOLE OF PROPER DIAMETER AND DEPTH USING A CARBIDE TIPPED DRILL OR CORING BIT AVOID ANY EXISTING REINFORCING...

Страница 47: ...urn for no more than thirty to sixty minutes and allowed to go out Do not refuel the fireplace during the second lighting Summary A twenty four hour cooling off period must be observed following secon...

Страница 48: ...fire to go out and the ashes to cool for at least six to eight hours After the cooling period carefully pick up the ashes from the firebox with a small metal fireplace shovel or other metal scoop and...

Страница 49: ...cal fireplace and chimney cleaners that are poured on a hot fire These can be Summary 49 dangerous and generally work only on the flue section nearest the fire leaving the rest of the flue unaffected...

Страница 50: ...ype Circle One Solid Wood Natural Gas Propane Fireplace Serial Number ________________________________________________________________________________ Located on Rating Plate Inside Fireplace Buyer __...

Страница 51: ..._______________________ ________________________________________________________________________________________________________ _______________________________________________________________________...

Страница 52: ...name address and phone number of the owner and 5 a brief description of the defect Earthcore or any division thereof is not responsible for any labor costs or indirect costs incurred for the replaceme...

Отзывы: