Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
32
Electrical Installation
LCDI CORD
Plug the integral supply cord (if provided) into an appropri-
ate receptacle or directly wire the appliance to the appropri-
ate electrical supply. Verify proper wiring of receptacle prior
to attaching supply cord. Incorrect wiring may impede
operation of unit.
Do not cut or remove the grounding prong from the plug.
When this appliance is installed, it must be electrically
grounded in accordance with local codes or in the absence
of local codes, with the National Electrical Code ANSI/
NFPA 70 and/or the CSA C22.1 Electrical Code.
HARDWIRE KIT
Cord connection to a wall socket is not permitted for 265
volt units. All 265 volt units must be hard-wired using the
Hardwire kit or make use of the plug-in receptacle in the
standard subbase.
LCDI CORDS
115V and 230/208V units are equipped with LCDI power
cords and can open the electrical circuit to the unit. In
the event the unit does not operate, check the reset button
located on or near the head of the power cord as part of the
normal troubleshooting procedure.
VOLTAGE MEASUREMENTS
Once the unit is properly wired, measure the unit supply
voltage. Voltage must fall within the voltage utilization
range as shown in the table below.
OPERATING VOLTAGE
UNIT VOLTAGE
RATING
VOLTAGE UTILIZATION RANGE
MINIMUM
MAXIMUM
115
103
132
230/208
197
253
265
238
292
Figure 31
LCDI Cord
Figure 32
Hardwire Kit