Performance Specifications
C. Subbase:
Subbase will support the wall sleeve when it extends
into the room more than 4 inches. Subbase must
come from the factory pre-assembled, with a built
in receptacle (size as specified on drawing schedule
and specifications) or with factory installed hardwire,
pre-sized for an exact fit to the unit.
1.02 qUALITY ASSURANCE
System shall be approved and certified by ETL.
Chassis capacity and efficiency performance shall be
certified in accordance with ARI standard 310/380.
Chassis shall meet ASHRAE Standard 90.1 for
minimum energy efficiency.
1.03 DELIvERY, STORAGE, AND HAN-
DLING
A. The packaging of the chassis shall be sufficient to
protect the chassis from damage during shipment via
an enclosed truck.
B. Chassis, wall sleeves, and grilles shall be shipped in
separate cartons. Universal handling instructions
shall be defined and visible on the carton, from front,
back and sides.
C. Unit shall be stored and handled per manufacturer’s
recommendations.
2.01 EqUIpMENT
A.
General:
Factory-assembled, single-piece heating and/or
cooling unit. Contained within the unit enclosure
shall be compressor, coils, fans and fan motor, heat-
ing means, controls, all wiring and piping, and a full
refrigerant charge (R410A).
B.
Chassis:
The chassis shall be a factory-assembled, single piece
heating and/or cooling unit, that is simple to install
and operate. Just slide the chassis into a wall sleeve,
plug it into an outlet, and operate after installation.
The chassis dimensions shall not exceed 42 in. wide
and 16 in. high with room cabinet in place. The
chassis shall consist of the following functional sec-
tions and components:
Direct Vent Gas-Fired
Packaged Terminal
Thru-Wall Air
Conditioner
pART I: SpECIFICATIONS
Size Range:
Cooling: 7,000 to 14,500 BTUh
Heating Output: 12,700 to 18,450 BTUh
pART II: GENERAL
1.01 SYSTEM DESCRIpTION
Single piece, thru-the-wall, electrically controlled unit using
a hermetic rotary compressor for cooling and gas heat.
A. Insulated Wall Sleeve:
Shall be entirely constructed of galvanized, heavy-
gauge steel with an Antique Ivory powder paint
corrosion-resistant finish. Wall sleeves shall be
installed through the wall as shown on plans and
shall have factory provisions for use of appropriate
fastening devices to secure sleeve to the wall. In no
event shall fasteners be installed through the basepan
in the bottom of the wall sleeve.
Wall sleeve shall provide excellent thermal insula-
tion, will have superior outdoor noise absorption and
be corrosion free for the life of the product.
B. Outdoor Louvered Grille:
Shall be (stamped) (architectural) anodized alumi-
num as shown on plans. Louver shall be (finished
natural) (painted) as shown on the schedule.
Louvers shall be easily installed from the inside of
the building after the cabinet/wall sleeve has been
installed. Special field fabricated louvers must be
approved by the PTAC manufacturer as to free area
and air circulation requirements.
Outdoor grille shall resist corrosion, breakage and
match the color specified on drawing schedule
specifications.